8. Press «Enter».
The output is assigned and activated.
9. Press the «Right» arrow.
10. Press «Enter».
The control field
Logic flashes.
11. Use «UP» or «Down» to set the desired behaviour, see table 77.
12. Press «Enter».
Result For messages at 24 V, the logic is set with the + symbol.
Result The pNloc measured value at the analogue AnMod_p_1 input is available as a message and as
output signal at the selected DOR output.
8.12.4 Switching and/or triggering messages with thresholds
Some measured values of the controller can be used for customised messages and/or other
switching functions.
The following measured values are available:
Measured value
Explanation
Message # Output
System pressure pNloc Threshold for pressure
System pressure pNloc (lo‐
cal network pressure at compressor output)
0095 O/W/A
Internal pressure pi
Threshold for pressure
Internal pressure pi (internal
pressure pi in the oil separator tank)
0093 O/W/A
ADT
Threshold for temperature
ADT (discharge tempera‐
ture)
0094 O/W/A
Inlet temperature
Threshold for temperature
Inlet temperature (inlet
temperature)
0092 O/W/A
PD temperature
Threshold for temperature
PD temperature (com‐
pressed air discharge temperature)
0096 O/W/A
n Compressor motor
1)
Threshold for the compressor motor speed
0098 O/W/A
1)
Power switching with frequency converter
Tab. 79 Available measured values
Example: Setting for the local network pressure at compressor output
System pressure pNloc.
Precondition Access level 2 is activated.
8
Initial Start-up
8.12 Setting input and output signals
No.: 9_9450 12 E
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
165