Installation
XHD Installation, Operation, and Maintenance Manual
38
Example: Discharge piping equipment
Correct
Incorrect
1.
Bypass line
2.
Shut-off valve
3.
Check valve
4.
Discharge isolation valve
1.
Check valve (incorrect position)
2.
The isolation valve should not be positioned
between the check valve and the pump.
Bypass-piping considerations
When to use a bypass line
Provide a bypass line for systems that require operation at reduced flows for prolonged
periods. Connect a bypass line from the discharge side (before any valves) to the source of
suction.
When to install a minimum-flow orifice
You can size and install a minimum-flow orifice in a bypass line in order to prevent bypassing
excessive flows. Consult your ITT representative for assistance in sizing a minimum-flow
orifice.
When a minimum-flow orifice is unavailable
Consider an automatic recirculation control valve or solenoid-operated valve if a constant
bypass (minimum-flow orifice) is not possible.