Cooling Requirements
The
Eserver
pSeries 670 requires air for cooling. As shown in
″
Proposed Floor Layout for Multiple
Systems
″
Eserver
pSeries 670 systems must face front-to-front. The use of a
raised floor is recommended to provide air through perforated floor panels placed in rows between the
fronts of systems (the cold aisles shown in the figure on page 156).
Note:
Do not place perforated tiles in the hot aisles. Heated exhaust air must exit the computer room
through the ceiling air-return system.
The following table provides system cooling requirements based on system configuration. The letter
designations in the table correspond to the letter designations in the graph shown in “Cooling
Requirements Graph” on page 160.
Number of I/O Drawers
(7040-61D)
1.1 GHz 4-way Module
(Cooling Chart Reference)
1.1 GHz 8-way Modules (Cooling Chart Reference)
8-way
16-way
1
A
A
A
2
A
A
B
3
N/A
N/A
C
Number of I/O Drawers
(7040-61D)
1.5 GHz 4-way Module
(Cooling Chart Reference)
1.5 GHz 8-way Modules (Cooling Chart Reference)
8-way
16-way
1
A
A
B
2
A
B
B
3
N/A
N/A
C
Chapter 2. Physical Characteristics of Systems
159
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...