3570 Model B02 and C02
Dimensions
Height
217 mm
8.5 in.
Height (with stand)
242.4 mm
9.5 in.
Width
483 mm
19.0 in.
Depth
771 mm
30.4 in.
Weight
Maximum
40.0 kg
88.2 lbs
Maximum (with stand)
44.8 kg
98.7 lbs
Electrical
Power source loading
0.13
(typical in kVA)
Voltage range (V ac)
100 to 127 or 200 to 240 (autoranging)
Frequency (hertz)
50 or 60
Thermal output
(typical)
444 Btu/hr
Power requirements
(typical)
130 watts
Power factor
0.99 (100 V ac) or 0.95 (200 V ac)
Inrush current
¹
30 amps at 120 V ac, 40 amps at 240 V ac
Maximum altitude
2135 m (7000 ft.)
Temperature
Requirements
Operating
16 to 32°C
(61 to 90°F)
Non-Operating
10 to 43°C
(50 to 109°F)
Humidity
Requirements
Operating
Non-Operating
(Noncondensing)
8 to 80%
8 to 80%
Wet Bulb
26°C(79°F)
27°C(81°F)
Noise Emissions
²
Operating
Idle
L
WAd
5.8 bels
5.5 bels
L
pAm
N/A
N/A
<L
pA
>
m
43dBA
38dBA
Impulsive noise
None
None
Prominent discrete
tones
None
None
Clearances
Front
Back
Left
Right
Install/Air Flow
³
76 mm (3 in)
76 mm (3 in)
None
None
Service
No additional clearance is needed for service.
1. Inrush current for each line cord. This model has two line cords.
2. See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
3. Air flow is 50 CFM.
248
Site and Hardware Planning Information
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...