7015 Model R30, R40, and R50
Dimensions
Height
267.0 mm
10.5 in.
Width
445.5 mm
17.5 in.
Depth
925.0 mm
36.4 in.
Weight
Minimum
59.7 kg
132 lbs.
(Configuration
dependent)
Electrical
Power source loading
0.8
(typical in kVA)
Voltage range (V ac)
200 to 240 or -48V dc
Frequency (hertz)
50 or 60
Thermal output
(typical)
2457 Btu/hr
Power requirements
(typical)
720 watts
Power factor
0.8 to 1.0
Inrush current
³
45 amps at 240 V ac
90 amps at 240 V ac with
redundant power option
Maximum altitude
2135 m (7000 ft.)
Temperature
Requirements
Operating
10 to 40°C
(50 to 104°F)
Non-Operating (Power Off)
10 to 40°C
(50 to 104°F)
Humidity
(Noncondensing)
Operating
Non-Operating (Power Off)
Without tape drive
8 to 80%
8 to 80%
With tape drive
20 to 80%
8 to 80%
Wet Bulb
Requirements
Without tape drive
27°C (80°F)
27°C (80°F)
With tape drive
27°C (80°F)
27°C (80°F)
Noise Emissions
1,2,4
Operating
Idle
L
WAd
6.4 bels
6.0 bels
L
pAm
N/A
N/A
<L
pA
>
m
49 dBA
47 dBA
Impulsive or
prominent discrete
tones
No
No
Clearances
Front
Back
Left
Right
Install/Air Flow
Maintenance of a proper service clearance should allow proper air flow.
Service
(See service clearances for the R00 System Rack)
1. See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
2. Noise emissions data for the Models R30, R40, and R50 CPU Media Enclosure are based on the following
configuration: the enclosure is mounted in a R00 System Rack and a power distribution unit is installed in the
rack and the system is operating in a nominal environment of 25°C (78 °F)
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
Chapter 2. Physical Characteristics of Systems
45
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...