7046 Model B50
Dimensions
Height
88 mm 3.5 in.
2 EIA Units
Width
447.0 mm 17.6 in.
Depth
751.8 mm 29.6 in.
Weight
Minimum
configuration
14.5 kg 32 lbs.
Maximum
configuration
15.9 kg 35 lbs.
Electrical
Power source loading
(maximum in kVA)
0.147
Voltage range (V ac)
100 to 127 or 200 to 240 (autoranging)
Frequency (hertz)
50 or 60
Thermal output
(maximum)
478 Btu/hr
Power requirements
(maximum)
140 watts
Power factor - US,
World Trade, Japan
0.95
Inrush current
²
40 amps
Maximum altitude
2135 m (7000 ft.)
Temperature
Requirements
³
Operating
10 to 40°C
(50 to 104°F)
Non-Operating
10 to 52°C
(50 to 126°F)
Humidity
Requirements
⁴
Operating
Non-Operating
(Noncondensing)
8 to 80%
8 to 80%
Wet Bulb
27°C (80°F)
27°C (80°F)
Noise Emissions
¹
Operating
Idle
L
WAd
5.2 bels
4.7 bels
L
pAm
N/A
N/A
<L
pA
>
m
35 dBA
30 dBA
Impulsive or
prominent discrete
tones
No
No
Clearances
Front
Back
Left
Right
Install/Air Flow
76mm(3 in)
76mm(3 in)
50mm(2 in)
50mm(2 in)
Service
Install so that it can be taken to an area providing 457mm(18 in) on the front and 457mm(18
in) on the left side.
4.
2. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
3. The upper limit of the dry bulb temperature must be derated 1 degree C per 137m (450 ft.) above 915m (3000
ft.).
4. The upper limit of the wet bulb temperature must be derated 1 degree C per 274m (900 ft. ) above 305m (1000
ft.).
Chapter 2. Physical Characteristics of Systems
207
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...