7026 Model H80 CEC Drawer
The Model H80 includes the Central Electronics Complex (CEC) Drawer with an I/O Drawer. For technical
information on the I/O Drawer, see “I/O Drawer 5 EIA” on page 79.
Dimensions
Height
218 mm 8.58 in. 5 (EIA Units)
Width
445 mm 17.5 in.
Depth
820 mm 32.3 in.
Weight
Minimum configuration
41 kg 90 lbs.
Maximum configuration
52 kg 115 lbs.
Electrical
Power source loading typical in kVA
0.32
Power source loading maximum in kVA
0.48
Voltage range (V ac)
200 to 240
Frequency (hertz)
50 or 60
Thermal output (typical)
1025 Btu/hr
Thermal output (maximum)
1536 Btu/hr
Power requirements (typical)
300 watts
Power requirements (maximum)
450 watts
Power factor
0.95
Inrush current
¹
40 amps
Maximum altitude
²
2135 m (7000 ft.)
Temperature Requirements
²
Operating
10 to 40°C
(50 to 104°F)
Non-Operating
10 to 52°C
(50 to 125.6°F)
Humidity Noncondensing
Operating
Non-Operating
Without tape drive
8 to 80%
8 to 80%
With tape drive
20 to 80%
8 to 80%
Wet Bulb Requirements
Without tape drive
27°C (80.6°F)
27°C (80.6°F)
With tape drive
23°C (73°F)
27°C (80.6°F)
Noise Emissions
³
Operating
Idle
With H80 CEC Drawer only
L
WAd
5.8 bels
5.8 bels
L
pAm
N/A
N/A
<L
pA
>
m
45 dBA
45 dBA
Impulsive or prominent discrete tones
No
No
Noise Emissions
³
Operating
Idle
With H80 and Primary I/O Drawer
L
WAd
6.2 bels
6.2 bels
L
pAm
N/A
N/A
<L
pA
>
m
48 dBA
48 dBA
Impulsive or prominent discrete tones
No
No
Install/Air Flow Clearance
Maintenance of proper service clearances should allow proper air flow.
Service Clearance
(See service clearances for the 7014 T00 Rack)
1. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
2. For altitudes above 915 meters, the maximum temperature limit is derated by 1 degree C for every 137 meters of
elevation above 915 meters.
3. See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
Chapter 2. Physical Characteristics of Systems
77
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...