Environmental Specification
Operating
Non-Operating
Storage
Shipping
Notes:
1. When an IBM-approved vapor bag and desiccant packets are used to protect the system, storage specifications
are valid for 6 months and shipping specifications are valid for 1 month. Otherwise, storage and shipping
specifications are valid for two weeks each.
2. The upper limit of the dry bulb temperature must be derated 1 degree C per 219 m (719 ft.) above 1295 m (4250
ft.). Maximum altitude for is 3048 m (10,000 ft.)
Weight Distribution
The following table shows dimensions and weights used to calculate floor loading for the
Eserver
pSeries
655. All floor-loading calculations are specified for a raised-floor environment.
1 Frame with Slimline Covers
1 Frame with Acoustical Covers
Weight without IBF
1501 kg (3303 lbs.)
1521 kg (3345 lbs.)
Weight with IBF
1642 kg (3612 lbs.)
1661 kg (3655 lbs.)
Width
750 mm (29.5 in.)
750 mm (29.5 in.)
Depth
1275 mm (50.2 in.)
1275 mm (50.2 in.)
Note:
These values may be used to calculate floor loading. Contact your installation planning representative for
more information about calculating floor loading for your system.
The following table shows floor-loading specifications for systems with slimline covers.
Floor Loading for Systems with Slimline Covers
a (sides)
mm (in.)
b (front)
mm (in.)
c (back
mm (in.)
Without IBF
kg/m
2
(lb./ft.
2
)
With IBF
kg/m
2
(lb./ft.
2
)
1
25 (1.0)
254(10.0)
254(10.0)
1123.2 (230.0)
1221.8 (250.2)
2
25 (1.0)
508 (20.0)
508 (20.0)
901.2 (184.6)
977.9 (200.3)
3
25 (1.0)
762 (30.0)
762 (30.0)
759.8 (155.6)
822.6 (168.5)
4
254 (10.0)
254 (10.0)
254 (10.0)
759.2 (155.5)
821.9 (168.3)
5
254 (10.0)
508 (20.0)
508 (20.0)
617.9 (126.6)
666.7 (136.5)
6
254 (10.0)
762 (30.0)
762 (30.0)
527.9 (108.1)
567.9 (116.3)
7
508 (20.0)
254 (10.0)
254 (10.0)
575.8 (117.9)
620.5 (127.1)
8
508 (20.0)
508 (20.0)
508 (20.0)
475.2 (97.3)
510.0 (104.4)
9
508 (20.0)
762 (30.0)
762 (30.0)
411.1 (84.2)
439.6 (90.0)
10
762 (30.0)
254 (10.0)
254 (10.0)
474.4 (97.2)
509.1 (104.3)
11
762 (30.0)
508 (20.0)
508 (20.0)
396.3 (81.2)
423.3 (86.7)
12
762 (30.0)
762 (30.0)
762 (30.0)
346.5 (71.0)
368.6 (75.5)
98
Site and Hardware Planning Information
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...