Chapter 7. Physical Characteristics of the 7100 Series
This chapter provides the physical characteristics for the 7100 series of external devices. The following
information can help you plan for your external devices. You need only do physical planning for the
devices you have ordered.
Note:
Footprints are not drawn to scale. Where a footprint is shown, the figure represents a top view of
the device.
7131 Model 105 SCSI Multi-Storage Tower
Dimensions
Height
407 mm
16.0 in.
Width (at pedestal)
197 mm
7.8 in.
Depth
483 mm
19.0 in.
Weight
Minimum
15.4 kg
34 lbs.
Maximum
20.0 kg
44 lbs.
Electrical
Power source loading
0.76 to 0.96
(typical in kVA)
Voltage range (V ac)
100 to 125 or 200 to 240 (selectable)
Frequency (hertz)
50 or 60
Thermal output (max)
1638 Btu/hr
Power requirements (max)
480 watts
Power factor
0.5
Maximum altitude
2135 m (7000 ft.)
Temperature Requirements
Operating
16 to 32°C
(60 to 90°F)
Non-Operating
10 to 43°C
(50 to 110°F)
Humidity Requirements
Operating
Non-Operating
(Noncondensing)
20 to 80%
20 to 80%
Wet Bulb
23°C (73°F)
27°C (80°F)
Noise Emissions
¹
Operating
Idle
L
WAd
(5 devices)
6.0 bels
5.6 bels
L
pAm
N/A
N/A
<L
pA
>
m
50 dBA
46 dBA
Impulsive or prominent discrete
tones
No
No
Clearances
Front
Back
Left
Right
Install/Air Flow
²
152 mm(6 in)
152 mm(6 in)
25 mm(1 in)
25 mm(1 in)
Service
152 mm(6 in)
N/A
N/A
25 mm(1 in)
Footprint
2
Width
250mm(9.8 in)
Depth
790mm(31 in)
1. See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
267
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...