Total System Weight (Kilograms)
Number of I/O
Subsystems
1
2
3
4
5
6
7
8
Slimline Doors
With IBF
1021
1095
1170
1648
1748
1823
1898
1973
Slimline Doors
Without IBF
846
921
996
1097
1481
1556
1631
1706
Acoustical Doors
With IBF
1034
1109
1184
1675
1775
1850
1925
2000
Acoustical Doors
Without IBF
872
947
1022
1137
1509
1583
1658
1733
No Doors With IBF
994
1069
1144
1595
1696
1770
1845
1920
No Doors Without
IBF
820
894
969
1044
1429
1504
1579
1653
Note:
Italicized numbers indicate single-frame systems.
Acoustical Noise Emissions
Acoustical Characteristic
Product Configuration
Declared A-Weighted Sound Power
Level, L
WAd
(B)
Declared A-Weighted Sound Pressure
Level, LpAm (dB)
Operating
Idle
Operating
Idle
7040 Acoustical Doors
7.5
7.5
57
57
7040 Slimline Doors
7.9
7.9
62
62
Notes:
1. Noise levels cited are for a typical configuration (A-Frame: Bulk Power, CEC cage, battery option, media drawer,
and two I/O drawers).
2. The 0.6-B (6-dB) reduction in noise emission levels with the acoustical rear door corresponds to a factor of 4
reduction. That is, the noise level of a single A-Frame with thin covers is about the same as the noise level of
four A-Frames with acoustical covers.
3. L
WAd
is the upper-limit A-weighted sound power level; LpAm is the mean A-weighted sound pressure level at the
1-meter bystander positions; 1 B = 10 dB.
4. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.
172
Site and Hardware Planning Information
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...