7028 Models 6C4 and 6E4
The Model 6C4 is a rack-mounted server system and the Model 6E4 is a deskside tower system.
Dimensions
Rack (Model 6C4)
Tower (Model 6E4)
Height
172.8 mm (6.8 in)
530 mm (20.9 in.)
4EIA Units
Width
444 mm (17.5 in.)
300 mm (11.8 in.)
Depth
609.6 mm (24.0 in.)
725 mm (28.5 in.)
Weight
Minimum configuration
32 kg (70.4 lbs.)
Maximum configuration
47.3 kg (104.8 lbs.)
Electrical
Power source loading (typical in kVA)
1-way, 2-way processors: 0.348, 4-way processor: 0.522
Power source loading (max. in kVA)
1-way, 2-way processors: 0.522, 4-way processor: 0.783
Voltage range (V ac)
100 to 127 or 200 to 240 (autoranging)
Frequency (hertz)
50 / 60
Voltage range (V dc)
Not supported
Thermal output (typical)
1-way, 2-way processors: 1129 Btu/hr, 4-way processor: 1693 Btu/hr
Thermal output (max.)
1-way, 2-way processors: 1693 Btu/hr, 4-way processor: 2540 Btu/hr
Power requirements (typical)
1-way, 2-way processors: 330 watts, 4-way processor: 500 watts
Power requirements (max.)
1-way, 2-way processors: 500 watts, 4-way processor: 750 watts
Power factor - US, World Trade, Japan
0.96
Inrush current
²
50 amps
Maximum altitude
³
,
⁴
2135 m (7000 ft.)
Temperature Requirements
³
Operating
5 to 35°C
41 to 95°F)
Non-Operating
10 to 52°C
(50 to 126°F)
Humidity Requirements
⁴
Operating
Non-Operating
(Noncondensing)
8 to 80%
8 to 80%
Wet Bulb
27°C (80°F)
27°C (80°F)
Model 6C4 Noise Emissions
1, 5, 6
Operating
Idle
L
WAd
6.1 bels
6.0 bels
<L
pA
>
m
44 dBA
43 dBA
Model 6E4 Noise Emissions
1, 7
Operating
Idle
L
WAd
6.0 bels
5.9 bels
<L
pA
>
m
42 dBA
41 dBA
Install/Air Flow
Maintenance of service clearance will allow proper air flow.
Service
See service clearances for the 7014 T00 Rack
4.
2. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
3. The upper limit of the dry bulb temperature must be derated 1°C per 137 m (450 ft.) above 915 m (3000 ft.).
4. The upper limit of the wet bulb temperature must be derated 1°C per 274 m (900 ft. ) above 305 m (1000 ft.).
5. Levels are for a single system installed in a T00 32 EIA rack with the center of the unit approximately 1500 mm
(59 in.) off the floor.
6. Levels apply to the following hardware configuration: 2 way 1 gigahertz processor, 3 Hard files, 2048 gigabytes of
RAM, Redundant system (Two 645 watt power supply, 2 processor fans).
7. Levels apply to the following hardware configuration: 2 way 1 gigahertz processor, 2 Hard files, 2048 gigabytes of
RAM, Non-redundant system (One 645 watt power supply, 1 processor fan).
8. All measurements made in accordance with ISO 7779 , and declared in conformance with ISO 9296.
82
Site and Hardware Planning Information
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...