The following table shows floor-loading specifications for systems with acoustical covers. The values
contained in the Condition column are described following the table.
Condition
a (sides)
mm (in.)
b (front)
mm (in.)
c (back
mm (in.)
1 Frame
kg/m
2
(lb./ft.
2
)
2 Frames
kg/m.
2
(lb./ft
2
)
1
25 (1.0)
135 (5.3)
135 (5.3)
1091.9 (223.6)
936.2 (191.7)
2
25 (1.0)
554 (21.8)
757 (29.8)
685.3 (140.4)
594.9 (121.8)
3
25 (1.0)
762 (30.0)
762 (30.0)
640.8 (131.2)
557.5 (114.2)
4
254 (10.0)
554 (21.8)
757 (29.8)
480.5 (98.4)
489.3 (100.2)
5
254 (10.0)
762 (30.0)
762 (30.0)
452.2 (92.6)
460.3 (94.3)
6
508 (20.0)
554 (21.8)
757 (29.8)
377.4 (77.3)
416.3 (85.3)
7
508 (20.0)
762 (30.0)
762 (30.0)
357.2 (73.2)
393.0 (80.5)
8
569 (22.4)
762 (30.0)
762 (30.0)
342.0 (70.0)
380.7 (78.0)
9
762 (30.0)
554 (21.8)
757 (29.8)
320.3 (65.6)
367.5 (75.3)
10
762 (30.0)
533 (21.0)
533 (21.0)
342.0 (70.0)
394.2 (80.7)
11
762 (30.0)
762 (30.0)
762 (30.0)
304.6 (62.4)
348.1 (71.3)
Definition of Conditions:
v
Condition 1 indicates maximum floor loading when systems are stored cover-to-cover on all four sides with covers
installed.
v
Conditions 2 and 3 indicate floor loading when the system has no side clearance (beyond side covers) on both
sides while front/back distances varied.
v
Conditions 4 through 8 indicate floor loading at various points below the maximum weight-distribution distance of
762 mm (30.0 in.) from each edge of the frame.
v
Conditions 9 through 10 indicate floor-loading options when the installation is limited to 342.0 kg/m
2
(70.0 lb/ft
2)
.
v
Condition 11 is the minimum floor loading required, based on the maximum weight-distribution area (30.0 in. from
each side of the base frame).
Notes:
1. Service clearance is independent from weight-distribution distance and must be at least 45 in. at the front of the
frame and 36 in. at the rear of the frame (measured from the base frame).
2. Weight-distribution areas should not be overlapped.
3. Floor-loading weight distribution distances should not exceed 762 mm (30 in.) in any direction when measured
from the base frame.
Floor loading for the system is illustrated in the Proposed Floor Layout for Multiple Systems in
“Considerations for Multiple System Installations” on page 192.
Chapter 2. Physical Characteristics of Systems
175
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...