SELF DIAGNOSIS FUNCTION
Procedure
(1)
Switch OFF
Press the air recirculation button over 5 times within
2 seconds during pressing the AUTO switch
All symbol of LCD blink 5 times
Error check
System OFF
Press AUTO switch
Cancelled diagnosis function(normal function)
Starting switch ON
3607A3CD69
Error check
The corresponding error code flickers on the setup temperature display panel, the other symbol
will turn OFF.
Error code flickers every 0.5 second.
If error code is more than two, each code flickers 2 times in sequence.
Error code
Fail safe function
8)
(2)
(3)
·
·
·
·
Error description
Fail safe function
Cabin inside sensor (11)
25˚C alternate value control
Ambient sensor (12)
20˚C
alternate value control
Duct (evaporator) sensor (14)
1˚C
alternate value control
Temp actuator (15)
If opening amount is 0 %, the alternate value is 0 %
If not, the alternate value is 100 %
Mode actuator 1, 2 (16, 17)
The alternate value is vent
Error code
Description
Error code
Description
11
Cabin inside sensor
16
Mode actuator 1
12
Ambient sensor
17
Mode actuator 2
14
Duct (evaporator) sensor
18
Intake actuator
15
Temp actuator
-
-