ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 1 - S
pecifications
A1 - 1
997-457-000-8, Issue 8
January 2010
Appendix 1 - Specifications
ID61/62 Series Panel
General:
This fire control panel is designed to comply with the
requirements of EN 54 Part 2/4. See Section 1.4 CE Marking
for further details. In addition to the basic requirements of
EN 54-2, the panel may be configured to conform with optional
requirements as described in Section 1.5 EN 54 Functions.
Mechanical:
Construction:
Sheet steel enclosure carries all
displays and controls under a steel
sheet cover.
Dimensions (mm) - including front cover(s)
ID61:
500(w) x 400(h) x 133(d)
ID62:
500(w) x 620(h) x 232(d)
Approx. Weight (no batteries):
ID61:
9kg
ID62:
15kg
Environmental:
Climatic classification: 3K5, (IEC 721-2-3)
Operating temperature: -5
o
C to +45
o
C,
(recom5
o
C to 35
o
C)
Humidity:
5% to 95% R.H.
Height above sea level: Maximum, 2000m
Panel sealing:
IP 30, (EN 60529)
Vibration:
EN 60068-2-6, 10-150Hz at
0.981ms
-2
(Meets the requirements
of EN 54-2/4)
EMC:
Emissions:
EN 61000-6-3
Immunity:
EN 50130-4
Safety:
EN 60950
Displays and Indications:
Alphanumeric display:
2 line x 40 character, backlit LCD.
LED Status Indicators: FIRE, DISABLEMENT, TEST,
FAULT, DELAYS ACTIVE, FIRE
OUTPUT: FAULT/DISABLED, FIRE
OUTPUT ACTIVE, PLANT ALARM,
POWER, FAULT, POWER SUPPLY
FAULT, EARTH FAULT, SYSTEM
FAULT, SOUNDER: FAULT/
DISABLED, PRE-ALARM, FIRE
CONTROL O/P: FAULT/DISABLED.
Zone Indicators:
Individual FIRE and Fault
indicators for 16 zones.