ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
83
997-457-000-8, Issue 8
January 2010
5.7.2 Filter-by-Type
This option is available with the Fire, Fault, Pre-alarm
and the Extinguishing System rules. The Filter-by-type
option has five selections with Fire and Fault categories:
ANY, OTI, AVS, MCP and MON and three with Pre-alarm:
ANY, OTI and AVS. The Filter-by-type option, when used
with the Extinguishing System category has seven
selections: Smoke/Heat, Sensor and MCP/ZMX, VIEW/
Sensor, Any Two Zones, Any Two Sensors, Any Single
Sensor and Any Single Module. Refer to
Section 5.7,
Control-by-Event Output Rules
for further information.
To select the type filter for Fire, Fault or Pre-alarm:
1
Press the ‘
2
’ button (using the numeric keypad) to
select the Filter option from the menu below.
2
Press the ‘
2
/
8
’ buttons to select the required filter.
3
Confirm the selection by pressing the ‘
5
’ button. To cancel
the selection, press ‘
4
’ button.
Extinguishing System
To select the type filter for Extinguishing System:
1
Press the ‘
2
’ button (using the numeric keypad) to
select the Filter option from the menu below.
2
Press the ‘
2
/
8
’ buttons to select the required filter.
3
Confirm the selection by pressing the ‘
5
’ button. To cancel
the selection, press ‘
4
’ button.
CBE Rule:01
1:Type
2:Filter
3:Evac
4:Silence
5:Interrupt
¦
: More
CBE Rule:01
Current Filter Type =
[ANY]
¦
: Change Filter Type
: Accept
< : Cancel
5
2
or
8
2
CBE Rule: 01
1:Type
2:Filter
8:Soak Timer
9:Zones
5
2
or
8
2
CBE Rule:nn
Ext. Filter Type = [One sensor]
: Accept
¦
: Change Filter Type
< : Cancel
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.