ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 1 - S
pecifications
A1 - 4
997-457-000-8, Issue 8
January 2010
Sounder Output Rating
Type:
Voltage reversal.
Output voltage:
20 to 28V (when active)
Maximum load:
700mA per sounder - 1A total
across all four sounder circuits.
Fuse rating:
Electronic over-current protection.
Monitoring:
Open- and short-circuit with
resistor EOL device. Partial-open
and parial-short-circuit with diode
EOL device fitted.
Volt-free Contact (VFC) Output Rating
Type:
Single-pole change-over
Maximum load:
Contacts rated 30V 1A
Fuse rating:
Not applicable
Switched -VE Output Rating
Output voltage:
20 to 28V
Maximum load:
83mA (total for both outputs)
Loop Output
Output voltage:
22.5 to 26.4V
Maximum load*:
0.5A
Max. loop impedance**: 20 ohms (-ve cable only, with
duplicate address detection) or
40 ohms (-ve cable only, without
duplicate address detection).
Max. loop capacitance: 0.5
μ
F
Up to 198 loop devices (up to 99 sensors and 99 modules) may
be fitted to the analogue loop.
The communication with devices on the loop can use either the
Notifier ‘CLIP’ or OPAL polling protocol. Refer to
Hardware
Recommendations
for a list of compatible devices and loading
limitations.
RS485 Serial Port (Optional)
Isolation:
Functional at 30V.
Baud rate:
1200 Baud.
Connector:
Terminal block on RS485 Isolated
Interface PCB.
Maximum cable length: 1200metres (minimum of 1.5mm
2
screened cable recommended)
** Use the following loop driver source
impedance values for panel calculation
purposes: 3.8R at 22.5Vdc
Outputs:
a. One Sounder or ÜE drive output (menu selectable -
ÜE not used in this application).
b. One dedicated Sounder output.
c. Two Sounder or Volt-Free Contact (VFC) outputs
(selectable).
d. Two open drain (switched -VE) outputs.
e. One loop output.
f.
One DC auxiliary output (two sets of terminals).
5
The panel (software version 5.04, or later)
is compatible with the Loop Booster
Module (LBM). The LBM provides
additional power to the loop for output
modules during panel alarm conditions.
Refer to the instructions (997-509-000-X)
provided with the LBM for a complete
technical specification.
* The Notifier Loop and Battery
Calculator
5
Support Tool, should be
used to ensure that the system is NOT
overloaded.