ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 1 - S
pecifications
A1 - 3
997-457-000-8, Issue 8
January 2010
Batteries:
Internal batteries:
Two 12V, sealed, lead-acid types
MUST be used.
Note:
Battery lifetime depends on the ambient temperature;
refer to the battery manufacturer’s technical
specification for guidance. (Refer to ‘Panel Ratings -
Fully Loaded’ for charger limitations).
Maximum battery ratings:
ID61:
12Ah
ID62:
38Ah
Panel Current:
Unloaded:
Main Board
Quiescent
3
:
70mA
Alarm
4
:
130mA
Printer (optional)
Quiescent:
11mA
Printing:
200mA (Average)
Isolated RS485 Board (optional)
Maximum:
25mA (Average)
PSU operating current (when PSU is powered
by batteries):
60mA
Fully Loaded:
Quiescent:
2.9A
Alarm:
3A
Fuses:
The location of the panel fuses is given here, together with their
ratings and their type.
a. MF1
Mains Supply
T 5A H 250V
b. FP2
Battery Charger Fuse
T 6.3A H 250V
T = time delay (i.e. anti-surge), H = high break capacity ceramic,
as defined by EN 60127.
Cables should be capable of carrying a minimum 1A.
Fuse rating:
Not applicable
TEMP
SNSR
+
-
+
-
CHGR
INH
N/C N/O
COM
b
a
DC Auxiliary Rating
Output voltage range:
20 to 28V
Maximum load
2
:
0.25A
Cables should be capable of
carrying a minimum 1A.
Fuse rating:
Not applicable
2
Total AUX DC power available - split
across both AUX and FBF outputs.
3
Back light off
4
Back light on, fire relay and two sounder
relays on.
Panel PSU input range:
Non-boosted - 19.9 -28.5Vdc
Boosted - 26.0 -28.3Vdc