ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
45
997-457-000-8, Issue 8
January 2010
2
Press the ‘
2
/
8
’ buttons to step through the Device
Options until the Pulse On/Off Ratio screen is displayed.
3
Press the ‘
6
’ button to change the required setting
to either 1/1 or 4/1.
4
Press ‘
4
’ to return to the Setup menu screen.
5.5.3.3 Auto High Test
The Auto High Test setup menu configures the panel to
test each device on the loop at a specified time. The test
checks that each device is able to produce an alarm
reading at the panel. To configure the Auto High Test:
1
From the Setup menu screen, using the numeric keypad
press the ‘
3
’ button to enter the Device Options menu.
2
Press the ‘
2
/
8
’ buttons to step through the Device
Options until the Auto High Test screen is displayed.
3
Press the ‘
6
’ button to enter (edit) the time at which
Auto High Test will start.
4
Using the numeric keypad, enter an appropriate start
time in the 24-hour clock format and confirm the set
time using the ‘
5
’ button. The LCD automatically returns
to the Auto High Test screen. Alternatively, press ‘
4
’ to
cancel all changes and return to the Auto High Test screen.
6
[Setup]
Pulse On/Off ratio = 4/1
> : Change
¦
: More
< : Exit
or
8
2
[Setup]
Pulse On/Off ratio = 1/1
> : Change
¦
: More
< : Exit
or
8
2
6
5
4
[Setup]
Auto High Test = 07:46
> : Change
1 : Disable
¦
: More
< : Exit
[Setup]
Auto High Test = DISABLED
> : Change
1 : Disable
¦
: More
< : Exit
3
[Setup]
Auto High Test = DISABLED
> : Change
1 : Disable
¦
: More
< : Exit
[Setup]
Auto High Test = DISABLED
Enter start time :
-0:00
< : Cancel
[Setup]
Device Blinking = ON
> : Change
¦
: More
< : Exit