ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
71
997-457-000-8, Issue 8
January 2010
5.6.1.4 AUX Action
An input device assigned to zones 17 to 32 is treated as
a Plant alarm input and given the default type of AUX.
The auxiliary action specifies which of the following
actions takes place with the operation of an AUX input:
i
Plant Alarm - non-latching
ii Panel Reset
iii Silence Sounders
iv Mute Buzzer
v Class Change
vi Abort Switch - latching
vii Hold switch - non-latching
viii Fire Brigade Called
ix Extinguishing System Released
x Extinguishing System Fault
To ensure recognition by the panel, the input device must
be active for at least 5 seconds (longer if not priority-polled).
To select the required auxiliary action:
1
Using the numeric keypad, press ‘
3
’ at the module
edit screen to select the auxiliary ‘Action’ option (the
default action is PLANT).
2
The screen displays action options as follows:
Press the ‘
2
/
8
’ buttons to display other AUX action
options, as appropriate.
3
Press the appropriate numeric pushbutton to select the
required action, e.g. Abort Switch. The display confirms
the selection and returns to the module edit screen:
Press the ‘
4
’ button to exit the module edit screen.
[Module nn - AUX] 1: Zone (17)
3: Action (PLANT) 4:[
Blank/Existing Text ]
[Module nn - Action] 1: Plant Alarm
2: Reset Panel
3: Silence Sounders
¦
: More
[Module nn - AUX] 1: Zone (17)
3: Action (ABORT) 4:[
Blank/Existing Text ]
The first 30 modules (from
lowest address upwards)
restricted to types MCP, DKM,
ZMX, MRL, IRL and all AUX
actions except Plant Alarm, are
added automatically to a
priority poll list. Subsequent
modules are polled normally.
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
[Module nn - Action] 4: Mute Buzzer
5: Class Change 6: Abort Switch
¦
: More
[Module nn - Action] 7: Hold Switch
8: Fire Brigade Called
¦
: More
[Module nn - Action]
9: Ext. System Released
¦
: More
[Module nn - Action]
10: Ext. System Fault
¦
: More
Action (PLANT)
Plant Alarm
Action (RESET)
Reset action
Action (SIL. )
Silence outputs
Action (MUTE )
Mute action
Action (CLASS)
Class Change
Action (ABORT)
Abort switch
Action (HOLD)
Hold switch
Action (FBCLD)
Fire Brigade Called
Action (ESREL)
Extinguishing System
Released*
Action (ESFLT)
Extinguishing System
Fault*
Action (FRFLT)
Fault Routing
Transmission Fault**
AUX Actions
Description
*
Monitored for short-circuit faults.
**
The indication of a fault routing transmission
fault is dependent upon the third-party fault
routing equipment being configured to
provide an appropriate input.
[Module nn - Action]
11: Fault Routing Fault
¦
: More