ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Installation Guide
11
997-457-000-8, Issue 8
January 2010
2.5 Dismantling the Panel
For installation purposes, it is recommended that the
cover(s) is(are) removed from the back box and stored
in a safe place until ready for commissioning.
If any other trades, e.g. plasterers or decorators, will be
working in the vicinity after fitting the ID61/62 Series Panel,
it is strongly recommended that before re-fitting the
cover(s) you remove the panel electronics and store in a
safe place until ready for commissioning. The main
components within the ID61/62 Series Panel are shown
below.
ID61/62 Series Panel Assembly
A
Back box (ID61 or ID62)
B
Chassis assembly
C
Cover (ID61/62)
D
Cover (ID62 only)
2.5.1 Removing the Cover(s)
To remove the ID61/62 Series Panel cover(s), it is
recommended that the following procedure is carried out
on a work bench BEFORE siting the panel on the wall:
1
Use a 4mm hexagonal socket key to unscrew each
of the M6 screws.
2
Carefully withdraw the cover away from the back box,
until the earth blade terminal within the cover (top right-
hand corner) is accessible.
3
Carefully detach the shrouded earth lead spade
terminal from the earth blade terminal located on the
inner side wall of the cover.
Note:
All blade connections to earth incorporate a locking
barb. To make a connection push the shrouded
receptacle on to the earth blade (1). To remove this
connection, pull the shroud (2), NOT the earth wire.
4
Remove and store the cover(s) in a safe place.
The power supply ratings label (view ‘A’) is affixed to the
inside face of the fire control panel cover.
Before installing the back box, remove the panel
electronics (see
Section 2.5.2, Panel Electronics
).
A
B
C
D
‘A’
NOTIFIER
by Honeywell
NF30
ID51
ID52
ID61
ID62
NF50
NF30-S
NF50-S
230VAC, 50Hz, 1.6A
A