ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
80
997-457-000-8, Issue 8
January 2010
EN54-2 : 7.11.d.
Configured delays MUST
be set to interruptable
(Y) to remain EN54
compliant
d.
Thermal Mode rule. This CBE rule activates assigned
outputs when the thermal element of multi-criteria
devices (OPX/SM2, SM3 and SM4) goes into alarm.
e.
Extinguishing System - System Fault. This CBE
rule lights the Extinguishing System Fault LED, if
provided, when a PLANT Alarm zone, with AUX
action EXT. SYSTEM FAULT, has been activated.
Each of the CBE Output Rules have various configurable
states available, dependent on the rule type. These
states are described below:
a.
Filter-by-type
- options are ANY (all types), OTI (Optical,
Thermal, Ionisation or MULTI /OPX /SM2, SM3
or SM4
sensor), AVS (see
Appendix 3
), MCP (manual call point),
MON (monitor module). Extinguishing System options are
Smoke/Heat, Sensor and MCP/ZMX, VIEW/Sensor, Any
Two Zones, Any Two Sensors, Any Single Sensor and Any
Single Module. Output will only operate if the input is
received from a device of the selected type.
b.
Evacuate (EV)
- has two options Yes (Y) or No (N). If
set to Y(es) assigned outputs activate when the END
DELAY/EVACUATE pushbutton is operated. Outputs
will not operate when this option is set to N(o).
c.
Silenceable (SL)
- has two options Yes (Y) or No
(N). If set to Y(es) assigned outputs will silence when
the SILENCE / RESOUND pushbutton is operated.
If set to N(o) the outputs will only silence after being
activated when the RESET pushbutton is operated.
d.
Interruptable (IN)
- has two options Yes (Y) or No (N). If set
to Y(es) operating the END DELAYS/EVACUATE pushbutton
cancels currently operating delays and assigned outputs
activate. If set to N(o), delays are NOT interruptable. The
delays can only be cancelled by another qualifying alarm
condition. This configuration does not comply with EN54
regulations.
e.
Class Change (Cl)
- has two options, Yes (Y) or No (N).
If digital input 1 is set to Class Change (see
Section 5.5.3.8 Digital Input 1) and the CBE Class
Change option is set to Y(es), then the assigned outputs
operate when digital input 1 is made. If set to N(o), digital
input 1 (set to Class Change) does not operate the
assigned outputs.
f.
Two Zone (Tz)
- has two options Yes (Y) and No (N).
If set to Y(es), at least two zones must be active
before the CBE rule is triggered.
g.
Zones
- determines the output response to fire or
plant alarms on a zone by zone basis using two
options: Zones 01 to 16 and Zones 17 to 32.
i
Zones 01 to 16 - addresses the Fire rule silence
options. Each zone can be configured as:
• N(o) - the zone is NOT included in the CBE Rule,
outputs will NOT be activated.
• Y(es) - the zone is included in the CBE Rule. An alarm
in this zone activates the outputs immediately.
CBE nn [THERMAL][ANY] 1 - - - - - - - - - - - - - - - - - - - - 1 6
1 : Change
[EvSlln
] YYYYNNYYYYYNYYNN
CBE nn [ES SYSFLT]
1 : Change