5.6.3.1 Output Type Setting
This option allows the configuration of the panel’s on-
board output circuits. To change the configuration:
1
Press the ‘
1
’ button on the numeric keypad. The
LCD prompts for the selection of an output type:
Note:
The options are Monitored Output Circuit Sounder
(SDR - default setting), High-load Monitored Output
Circuit Sounder (SDH), Transmission Device (TxD),
Monitored Output Circuit Relay (CTL), Monitored
Output Circuit Relay
1
(CTE), Unmonitored Output
Circuit (RLY), Unmonitored Output Circuit
1
(RLE) and
extinguishing system output types (EST, ESO, ESE).
2
To select the new type, using the numeric keypad
press the ‘
1
’, ‘
2
’ or ‘
3
’ button as required.
Note:
Only those types valid for the chosen output are
available. The panel’s -VE Outputs (B05/B06) are
unmonitored and are thus fixed as type ‘RLY’.
5.6.3.2 CBE Rule Setting
This option allows each of the panel’s on-board output circuits
to be assigned to a CBE Rule range. Refer to Section
5.6.1.5 CBE Rules for more details on range setting. To
change the CBE Base Rule, proceed as follows:
1
Using the numeric keypad press the ‘
2
‘ button to
select the CBE Rule option:
2
You are now prompted to enter a new CBE Base Rule.
Use the numeric keypad to enter the CBE Rule
required for the output circuit and use the ‘
5
’ button
to confirm the selection.
Refer to
Section 5.7, Control-by-Event Output
Rules
for information concerning the CBE Rules. The
rule defines whether the output will respond to zonal
alarms and/or the END DELAY / EVACUATE
pushbutton. It also determines whether the output is
silenceable and whether any delays are interruptable.
EN 54-2 : 7.7.1
One output on the panel
must be configured as a
fire output. This may be
an unmonitored relay
output.
[ON-BOARD]
B01 (SDR)
3: Mon. : RES.
1 : Type
2 : CBE Rule (01)
¦
: Change < : Exit
Use the ‘
2
/
8
’ buttons
to change the output
circuit being configured
2
[BOn] CBE Rules
01 - - - - - - - - - - - - --- - - - - - - - 1 6
1 : Base [01 : No]
YYYYYYYYYYYYYYYY
[BOn] CBE Rules
01-----------------------24
Enter CBE Rule :
_
<: Cancel
[ON-BOARD]
B01 (SDR)
>SDR<RLY CTL TxD RLE CTE EST ESO ESE S
1
[ON-BOARD]
B0n (AAA)
3: Mon. : RES.
1 : Type
2 : CBE Rule (nn)
¦
: Change < : Exit