ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
48
997-457-000-8, Issue 8
January 2010
[S1
Setup]
1: Panel Options
2: Site Details
3: Device Options
¦
: More
[Setup]
Device Blinking = ON
> : Change
¦
: More
< : Exit
5.5.3.8 Extinguishing System Delay
TThe extinguishing system delay allows an evacuation period
of up to 180 seconds to be entered (default 60 secs, minimum
of 10 secs). To configure the delay, proceed as follows:
1
From the Setup menu screen, press the ‘
3
’ button on
the numeric keypad to enter the Device Options menu.
The Device blinking screen is displayed first.
2
Press the ‘
2
/
8
’ buttons to step through the Device
Options until the Ext. System Delay screen is
displayed. Press the ‘
6
’ button to change the delay
time. The display then prompts you for the new value:
3
Enter the required delay time using the numeric
buttons, e.g. 30 secs:
4
Press the ‘
5
’ button to confirm and return to the
Setup menu screen.
5.5.3.9 Extinguishing System Soak
To specify for how long the extinguishing system operates
after being turned on:
Note:
The timer will only be triggered by CBE rules that
have the
Soak Timer Enable
activated.
1
From the Setup menu screen, press the ‘
3
’ button
on the numeric keypad to enter the Device Options
menu. The Device Blinking screen is displayed first.
2
Press the ‘
2
/
8
’ buttons to step through the Device
Options to display the Ext. System Soak screen.
3
Press the ‘
6
’ button. The display then prompts you
for the new value:
[Setup]
Ext. System Soak =
0 Seconds
> : Change
¦
: More
< : Exit
3
or
8
2
[Setup]
Device Blinking = ON
> : Change
¦
: More
< : Exit
[S1
Setup]
1: Panel Options
2: Site Details
3: Device Options
¦
: More
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
3
[Setup]
Ext. System Delay =
60 Seconds
Enter new value 30
: Confirm
< : Cancel
6
or
8
2
[Setup]
Ext. System Delay =
60 Seconds
Enter new value __
: Confirm
< : Cancel
[Setup]
Ext. System Soak =
0 Seconds
Enter new value __
: Confirm
< : Cancel
6