ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Commissioning
33
997-457-000-8, Issue 8
January 2010
3
Using the numeric keypad, press ‘
6
’ to select the
Commissioning option and confirm using the ‘
5
’
pushbutton. The Commissioning option is
automatically displayed if a Level 3 passcode was
previously entered.
If a Level 2 passcode was entered the LCD prompts:
4
Enter the correct Level 3 passcode using the numeric
keypad and confirm using the ‘
5
’ pushbutton (or
press ‘
4
’ to cancel the last operation).
4.7 Commissioning Tests
The following paragraphs list tests that should be performed
after configuration has been completed. A successful result
from these tests indicates that the panel is working properly.
4.7.1 Test LEDs
This procedure is described in the
ID61/62 Series Panel -
Operating Manual, 997-458-000-X, Section 4.8.1
.
4.7.2 Test LCD
This procedure is described in the
ID61/62 Series Panel -
Operating Manual, 997-458-000-X, Section 4.8.2
.
4.7.3 Test Zones
This procedure is described in the
ID61/62 Series Panel -
Operating Manual, 997-458-000-X, Section 4.8.3
.
4.7.4 Test Auto High Test
This procedure is described in the
ID61/62 Series Panel -
Operating Manual, 997-458-000-X, Section 4.8.4
.
4.7.5 Test Outputs
This procedure is described in the
ID61/62 Series Panel -
Operating Manual, 997-458, Section 4.8.5
.
4.7.6 Test Buzzer
This procedure is described in the
ID61/62 Series Panel -
Operating Manual, 997-458-000-X, Section 4.8.6
.
4.7.7 Test Keyboard
This procedure is described in the
ID61/62 Series Panel -
Operating Manual, 997-458-000-X, Section 4.8.7
.
[S1 COMM]
1:Setup
2:Circuit
3:CBE Rules
4:Zones
5:Access
¦
: More
COMMISSION MODE ACCESS
Enter Level 3 Passcode: . . . .
< : BackSp
[S1 COMM]
1:Setup
2:Circuit
3:CBE Rules
4:Zones
5:Access
¦
: More
6
5