2.8 RS232 Interface Connections
The panel is fitted with a standard 9-way ‘D’-type RS232
Interface connector, located at the bottom left-hand
corner of the PCB assembly. The RS232 connector is
used for the following purposes:
a. Configuration using the PC Support Tool (refer to
997-405, ID61/62 Series Panel - Offline
Configuration Manual
).
b. Upgrading the Panel Software (refer to
997-415, ID61/
ID62 Series Panel - Upgrading Instructions
).
Before starting any of the above operations ensure
suitable anti-static precautions have been taken.
The RS232 connector has the following pin out:
Pin
Description
1
Data Carrier Detect (DCD)
2
Receive (RX) Data
*
3
Transmit (TX) Data
*
4
Data Terminal Ready (DTR)
5
GND
*
6
Data Set Ready (DSR)
7
Request To Send (RTS)
*
8
Clear To Send (CTS)
*
9
Not Applicable
Note:
Pin numbers marked thus ‘*’ are the only
required connections. Any others fitted will
be ignored.
A Data Transfer Lead (PN: 082-173) is required. Jumpers
must be removed as follows:
1
Remove the cover [refer to
Section 2.5.1, Removing
the Cover(s)
] to access the panel electronics.
2
Remove the Jumper Links JP6, E_FLT (earth fault
monitoring) and JP7, MEM (configuration lock).
Note:
Refer to
Section 4.3.1 Jumper Link Options/
Earth Fault Monitoring
(JP6) when connecting
third-party equipment to the panel.
3
Fit the Data Transfer Lead to the RS232 Interface
socket connector, SK3.
4
Perform required operation.
5
After satisfactory completion disconnect the lead and
then fit the jumpers.