ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
54
997-457-000-8, Issue 8
January 2010
1
From the Peripheral Options screen, press the ‘
1
’
button on the numeric keypad to select the RS485
Communications port option. The RS485 Protocol
setup screen is displayed:
2
Press the ‘
2
/
8
’ buttons to scroll through the Setup
menu until the Suspend Comms Limit screen is
displayed.
3
Press the ‘
6
’ button if the limit is to be changed.
4
Using the numeric keypad, enter the new value (in
minutes) and confirm using the ‘
5
’ button. The LCD
automatically returns to the Suspend Comms Limit
screen. Alternatively, press ‘
4
’ to cancel the change.
5.5.4.6 RS232 Protocol
This option enables the protocol of the RS232 port to be
configured for use with the following driver:
a. External printer (default selection).
b. Third party equipment
c. GSM Modem.
1
From the Peripheral Options screen, press the ‘
2
’
button on the numeric keypad to select the RS232
Communications port option. The RS232 Protocol
setup screen is displayed:
2
Press the ‘
6
’ button to toggle between ‘PRINTER’
and ‘THIRD PARTY’.
3
Press ‘
4
’ to return to the Peripheral Options menu
screen.
5.5.4.7 Print Control or Third Party
This option is dependent upon the selected RS232
operating mode (see
Section 5.5.4.6
).
If the RS232 port is set to PRINTER, the available ‘Print
Control’ options are:
a. BASIC - slow mode, no handshaking (default option).
[Setup]
RS485 Protocol = THIRD PARTY
> : Change
¦
: More
< : Exit
[Setup]
Suspend Comms Limit =
0 mins
> : Change
¦
: More
< : Exit
or
8
2
[Setup]
Suspend Comms Limit =
0 mins
Enter new value 60
: Confirm
< : Cancel
6
1
6
[Setup]
RS232 Protocol = THIRD PARTY
> : Change
¦
: More
< : Exit
[Setup]
RS232 Protocol = PRINTER
> : Change
¦
: More
< : Exit
2