Configuration Mode
66
997-457-000-8, Issue 8
January 2010
If no device is found at the selected address, the LCD
displays one of the messages below:
A specific address can only be configured if:
a. A device has previously been auto-learnt at the
address, or
b. The off-line tool was used to configure the device type
present.
Sensors
The following sensor configuration settings are selectable:
a. The assigned zone (see
Section 5.6.1.1, Zone Setting
),
b. The sensor sensitivity (see
Section 5.6.1.2, Sensor
Sensitivity Setting
), and
c. The device text string (see
Section 5.8, Zone Texts
).
Input Modules
The following input module configuration settings are
selectable:
a. The assigned zone (see
Section 5.6.1.1, Zone Setting
),
b. The type of input device (MCP, DKM, MON, ZMX, MNS,
MRL, IRL; Extinguishing System inputs: AUX - Hold Switch
and Abort Switch (see
Section 5.6.1.3, Type Setting
),
Note:
The AUX device types CANNOT be changed.
c. The device text string (see
Section 5.8, Text Editing
).
Output Modules
The following output module configuration settings are
selectable:
a. The assigned zone (see
Section 5.6.1.1, Zone Setting
),
b. The type of output device (SDR, SDH
1
, CTL, RLY,
EST
2
, ESO
2
, ESM, TxD, ESE
2
, RLE
2
and CTE
2
) (see
Section 5.6.1.3, Type Setting
).
1
Sounders enabled with high-load monitoring function.
2
These output device types are subject to extinguishing
system disablement if the option to automatically
disable transmission and extinguishing system
devices is configured (refer to Section 5.5.3.14 TD/
ES Disablement at Access Level 2).
c. The CBE Rule number. It is NOT possible to change
the configuration of the associated CBE Rule.
[Sensor]
Snn (xxx) No device learnt
[Module]
Mnn (xxx) No device learnt
[Sensor nn - AAA] 1 : Zone (nn)
3 : Sensitivity
4 : [
Blank/Existing Text
]
[Module nn - AAA] 1 : Zone (nn)
2 : Type
3:CBE Rule (nn) 4 : [
Blank/Existing Text
]
or
2
1
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
ESE
Extinguishing System Trigger
(not monitored /not disabled by
FWP4)
EST
Extinguishing System Trigger
(not monitored)
ESO
Extinguishing System Output
(monitored)
RLE
Relay Output Module (not
monitored /disabled by FWP4)
CTE
Control Output Module
(monitored for open and short
circuits /disabled by FWP4)
Extinguishing System Outputs