5.7.5 Interrupt Delay
The Interrupt Delay option has two settings, Yes (Y) or
No (N). This option is only available with the Fire rule.
Caution: Selecting ‘No’ contravenes the
requirements of EN54.
To change the Interrupt setting from the CBE Output
Rules menu:
1
Press the ‘
5
’ button using the numeric keypad to
select the Interrupt option.
2
Press the ‘
6
’ button to select the required setting.
Refer to
Section 5.7, Control-by-Event Output
Rules
for further information.
3
Confirm the selection by pressing the ‘
5
’ button. To
cancel the selection, press ‘
4
’. In either case the
menu below is re-displayed.
5.7.6 Class Change
This control parameter has two options, Yes (Y) and No
(N). These indicate whether or not the selected CBE
Rule’s assigned outputs activate when Digital Input 1 is
configured as Class Change and then operated. To
configure Class Change, from the CBE Output Rules menu:
1
Press the ‘
6
’ button using the numeric keypad to
select the Class Change option.
2
Press the ‘
6
’ button to select the required setting.
Refer to
Section 5.7, Control-by-Event Output
Rules
for further information.
3
Confirm the selection by pressing the ‘
5
’ button. To
cancel the selection, press ‘
4
’. In either case the
menu below is re-displayed.
CBE Rule:01
1:Type
2:Filter
3:Evac
4:Silence
5:Interrupt
¦
: More
EN54-2 : 7.11.d.
Configured delays MUST
be set to interruptable
(Y) to remain EN54
compliant
CBE Rule:01
Interrupt = [N]
>:Change
:Accept
< : Cancel
CBE Rule:01
Interrupt = [Y]
>:Change
:Accept
< : Cancel
CBE Rule:01
1:Type
2:Filter
3:Evac
4:Silence
5:Interrupt
¦
: More
CBE Rule:01
6:Class Change
7:Two Zone
9:Zones
¦
: More
CBE Rule:01
Class Change = [N]
> : Change
: Accept
< : Cancel
CBE Rule:01
Class Change = [Y]
> : Change
: Accept
< : Cancel
CBE Rule:01
6:Class Change
7:Two Zone
9:Zones
¦
: More
6
5
5
6
5
6