ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
76
997-457-000-8, Issue 8
January 2010
5.6.2.1 Initialising OPAL Devices
OPAL protocol loop devices need programming, or initialising,
before the panel can perform a learn operation and permit
device polling. Device initilialisation is normally performed as
part of a learn operation. However, initialisation can be carried
out independently of a learn operation as described below.
Also, it is possible to display the loop device totals,
normally displayed after a learn operation, using the
LEARN menu option ‘Display Totals’.
1
Use the ‘
2
/
8
’ buttons to scroll to the second menu
display.
3
Press the ‘
5
’ pushbutton to confirm device
initialisation or press ‘
4
’ to cancel:
2
Press the ‘
4
’ pushbutton using the numeric keypad
to select ‘Initialise OPAL’. A request for initialise
confirmation is then displayed:
4
When initialisation is complete the second menu
screen is re-displayed:
5
To re-display the learn totals after an initialise
operation, use the numeric keypad and press the ‘
3
’
button to select the option ‘Display Totals’:
Note:
If this option is selected before a learn operation is
carried out or with a CLIP protocol loop the
following error message is displayed:
[S1 LEARN] 3 : Display Totals
4 : Initialise OPAL
¦
: More
[LEARN]
Confirm OPAL Device Initialise
: Continue <: Cancel
[Learn] Initialising OPAL Devices
[S1 LEARN] 3 : Display Totals
4 : Initialise OPAL
¦
: More
[LEARN] Total 010 (003 + 007)
¦
: More < : Exit
OPAL: OPT 03, SM2 02, SM3 01, M701 01
[LEARN]
No OPAL Devices Configuration
<: Exit
5
4
2
8
or
3