ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Commissioning
29
997-457-000-8, Issue 8
January 2010
Unmonitored Relays
The unmonitored relay Output C is factory set as a fault
output, and Output D as a fire output. When configured as
volt-free relay outputs, the outputs are NOT power-limited.
If these connections are to be configured as unmonitored
relays make sure that:
a. Jumper Links are set accordingly, refer to
Section 4.3.1, Jumper Link Options
,
b. Correct polarity is used when terminating at the back
box, i.e. terminal 1 being normally-open (or normally-
closed) and terminal 2 being common contact.
Maintain adequate segregation from power-limited
wiring.
4.4.6 -VE Outputs
The two -VE Outputs, located at TB6 at the top right-
hand corner of the PCB assembly, are normally used to
provide a DC power supply for up to two relays located
externally to the panel.
When the -VE Outputs are initially connected, the default
software outputs are set as follows:
a. Output 1 - Pre-Alarm and
b. Output 2 - Plant Warning.
During commissioning these outputs can be individually
configured to become active if any fire alarm, pre-alarm,
fault or plant warning conditions occur (see
Section 5,
Configuration
).
4.4.7 Digital / ÜE Inputs
These inputs are located at the top centre of the PCB
assembly. Digital Input 1 can be configured for use as
either a Day Mode or Class Change function. To select
the required function use the ‘Digital Input 1’ menu, see
Section 5.5.20 Digital Input 1
.
4.4.8 Switch Connections
KEY-SW
This connector is a pre-wired digital input on the PCB.
Operation of the keyswitch permits access at level 2. The
keyswitch also performs the actions as when the cover
switch operates (see below).
Cover Switch
The input on the PCB right edge marked COVER
SWITCH is used with the cover-off switch. Removal of
the cover will disable the ÜE device and output to the
Extinguishing System.
TB2
+
-
+
-
C
D
NC C NC C
TB2
+
-
+
-
C
D
NO C NO C
TB3
+
-
+
-
1
2
+
+ -
-
TB7
COVER
SWITCH
J4
KEY-SW
Input
2
Input
1
OUTPUT C
OUTPUT D
JP3
JP4
1
3
5
7
2
4
6
8
1
3
5
7
2
4
6
8
Output
2
Output
1
TB6
+
-
+
-
1
2
+
+ -
-