ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
69
997-457-000-8, Issue 8
January 2010
Optiplex/SM2, SMART 3 and 4 Multi-criteria Sensors
These sensors require smoke pre-alarm and alarm
sensitivity to be set as one of a number of available
sensitivity levels. The number of levels is dependent on
whether the device is part of a group. For SM2, SM3 and
SM4 the number of levels is dependent on whether the device
is part of a group.In stand-alone mode five levels are
available, L1 to L5, L1 being the most sensitive and L5
being the least sensitive. In a group the range is extended
to nine levels, L1 to L9. In addition, a lower sensitivity
level, L6
1
(or L9 in a group), which is a heat-sensing
function only, is available for use with a configured Day
Mode activity. Optiplex (OPX/SM2), SM3 and SM4 Multi-
Sensors can operate in stand-alone mode or form part of a co-
operative AWACS
TM
group.
1
OPX/SM2 sensor level 6 functionality is only possible with panel
software version 5.00, or above. SMART 4 and SMART3
sensor level 6 functionality is only possible with panel software
version 5.08, or above. OPX/SM2 and SM3 sensors must only
be used with LIB software version 9.00, or above. SMART 4
sensors must only be used with LIB software version 11.00, or
above.
Note:
Refer to Appendix 2 VIEW
TM
, Optiplex and SMART
Devices for details on setting the sensitivity level
of grouped Optiplex/SM2, SM3 and SM4 sensors.
To set the sensitivity of Optiplex/SM2, SM3 and SM4
sensors:
1
At the sensor attributes menu, press the ‘
3
’ button on the
numeric keypad to display the Sensor Sensitivity Setting menu:
2
Using the numeric keypad, press ‘
1
’ to select the
Alarm Sensitivity setting or press ‘
2
’ to select the
Day Mode Sensitivity setting.
3
At the appropriate prompt, use the numeric keypad to
enter the desired sensitivity level.
4
Press ‘
5
’ to confirm the level entered or press ‘
4
’
to cancel.
Note:
In either case you will be prompted to select the
pre-alarm sensitivity level. Select a new level, if
required, and press ‘
5
’ to confirm.
[Sensor nn - OPX]
Sensitivity
1 : Alarm(Lvl5)
2 : Day(Lvl5)
[Sensor nn - OPX]
Sensitivity
Enter new alarm level : ____
< : Cancel
or
2
1
1
2
[Sensor nn - OPX]
Sensitivity
Enter day mode alarm : ____
< : Cancel
[Sensor nn - OPX]
Sensitivity
1 : Alarm(Lvl)
2 : Day(Lvl5)
Note:
With newly-learnt multi-criteria
devices the sensitivity setting
defaults to level 5.