4-20
Input frequency Start/End
External analog signal from the control terminals
(frequency command)
O-L terminal : 0 - 10V
OI-L terminal : 4 - 20mA
O2-L terminal : -10 / 0 / +10V
Set output frequency for one of the above
(1)Start, End of O-L terminal, OI-L terminal
Set item
Function code
Data
Contents
O/OI start
A011/A101
0.00-400.0
Unit : Hz Set starting frequency
O/OI end
A012/A102
0.00-400.0
Unit : Hz Set ending frequency
O/OI start rate
A013/A103
0.-100.
Unit : %
Set start rate for external frequency command 0-10V, 4-20mA
O/OI end rate
A014/A104
0.-100.
Unit : %
Set end rate for external frequency command 0-10V, 4-20mA
00
External start frequency
Output frequency from 0 to A013/A103 outputs the value of
A011/A101
O/OI start
Selection
A015/A105
01
0Hz
Output frequency from 0 to A013/A103 outputs the value of
0Hz
When the input is from 0 to 5V with O-L terminal, set A014 to 50%.
(Example 1) A015/A105 : 00 (Example 2) A015/A105 : 01
(2) Start, End of O2-L terminal
Set item
Function
code
Data
Contents
Notes
O2 start
A111
-400.- 400.
Unit : Hz Set starting frequency
O2 end
A112
-400.- 400.
Unit : Hz Set ending frequency
O2 start rate
A113
-100.- 100.
Unit : % Set starting rate for external frequency command
–10-10V (Note 1)
O2 end rate
A114
-100.- 100.
Unit : % Set ending rate for external frequency command
–10-10V (Note 1)
(Example 3)
(Note 1) The rates of –10V-10V is following.
-10V- 0V:-100-0%
0V-10V:0-100%
For example, in case of use with O2-L terminal, set -50% to A113,
50% to A114.
A013/A103
Frequency
command
Maximum
frequency
A012/A102
A011/A101
0
A014/A104
100%
(0V/4mA)
(10V/20mA)
Frequency
command
Maximum
frequency
A012/A102
A011/A101
0
A013/A103
A014/A104 100%
(0V/4mA)
(10V/20mA)
Chapter4 Explanation of function
Forward
Maximum
frequency
Reverse
Maximum
frequency
A111
A114
A113
A112
+10V
-10V
(Example 3)
A011: O start
A012: O end
A013: O start rate
A014: O end rate
A015: O start selection
A101 : OI start
A102 : OI end
Relation code
A103: OI start rate
A104: OI end rate
A105: OI start selection
A111: O2 start
A112: O2 end
A113: O2 start rate
A114: O2 end rate