2-12
(4) Common applicable tools
Power lines
R,S,T,U,V,
W,P,PD,N
Earth line
G
External
resister
between
P and RB
Applicable tools
Motor
Output
(kW)
Applicable
Inverter
model
mm
2
or
more
AWG
or
more
mm
2
or
more
AWG
or
more
AWG
or
more
(
#5
)
mm
2
AWG
Screw
size of
terminal
Terminal
Tightning
Torque
max
(N•m)
Leak breaker
(ELB)
Circuit
breaker
or fuse
Electro-
magnetic
controller
(Mg)
11
L300P-110LF
14
4
14
4
10
5.5
8
M6
14-6
4.9
RX100(75A)
60A
H50
15
L300P-150LF
22
(
Note 1)
2
22
3
8
5.5
8
M6
22-6
4.9
RX100(100A)
70A
H65
18.5
L300P-185LF
30
1
22
3
8
-
-
M6
38-6
4.9
RX100(100A)
90A
H80
22
L300P-220LF
38
1/0
30
2
8
-
-
M8
38-8
8.8
RX225B(150A)
100A
H100
30
L300P-300LF
60
(Note 1)
2/0
30
2
6
-
-
M8
60-8
8.8
RX225B(200A)
150A
H125
37
L300P-370LF
100
(38
×
2)
(Note 1)
(
#1
)
50
1/0
6
-
-
M8
100-8
(38-8)
8.8
RX225B(225A)
175A
H150
45
L300P-450LF
100
(38
×
2)
(
#2
)
80
3/0
6
-
-
M10
100-10
(38-10)
13.7
RX225B(225A)
200A
H200
55
L300P-550LF
150
(60
×
2)
(Note 1)
(
#3
)
80
3/0
4
-
-
M10
150-10
(60-10)
13.7
RX400B(350A)
250A
H250
200
V
c
la
s
s
75
L300P-750LF
150
(60
×
2)
(Note 1)
(
#3
)
100
4/0
4
-
-
M10
150-10
(60-10)
13.7
RX400B(350A)
300A
H300
11
L300P-110HF
5.5
8
5.5
8
10
5.5
8
M6
5.5-6
4.9
EX50C(50A)
30A
H25
15
L300P-150HF
8
6
8
8
10
5.5
8
M6
8-6
4.9
EX60B(60A)
35A
H35
18.5
L300P-185HF
14
6
14
4
10
-
-
M6
14-6
4.9
EX60B(60A)
50A
H50
22
L300P-220HF
14
4
14
4
10
-
-
M6
14-6
4.9
RX100(75A)
50A
H50
30
L300P-300HF
22
3
22
3
10
-
-
M6
22-6
4.9
RX100(100A)
70A
H65
37
L300P-370HF
38
1
22
3
8
-
-
M6
38-6
4.9
RX100(100A)
80A
H80
45
L300P-450HF
38
1
22
1
8
-
-
M8
38-8
8.8
RX225B(150A)
100A
H100
55
L300P-550HF
60
1/0
30
1
6
-
-
M8
60-8
8.8
RX225B(175A)
125A
H125
75
L300P-750HF
100
(38
×
2)
(
#2
)
50
1/0
6
-
-
M8
100-8
(38-8)
8.8
RX225B(225A)
150A
H150
90
L300P-900HF
38
×
2
(
#2
)
50
3/0
6
-
-
M10
38-10
13.7
RX225B(225A)
200A
H200
110
L300P-
1100HF
60
×
2
(
#3
)
80
3/0
4
-
-
M10
60-10
13.7
RX400B(350A)
250A
H250
400
V
c
la
s
s
132
L300P-
1320HF
80
×
2
(
#3
)
100
4/0
4
-
-
M10
80-10
13.7
RX400B(350A)
300A
H300
#1
3/0 or 2 parallel of 1 AWG
#2
250kcmil or 2 parallel of 1 AWG(75ºC)
#3
350kcmil or 2 parallel of 1/0 AWG
#4
Use suitable fuse with an UL-listed for UL.
#5
Conformity to the UL
(Note)
Field wiring must be made by an UL-listed and CSA-certified closed-loop terminal connector sized for
the wire gauge involved. Connector must be fixed by using the crimping tool specified by the connector
manufacture or equivalent wording included in the manual.
(Note 1)
If wires are shorter than 10m and are located within an enclosure, it is possible to use following power
lines.
Power lines
Inverter
Model
mm
2
or
more
AWG
or
more
Heat
resistant
Terminal
150LF
14
4
110ºC
14-6
300LF
38
1/0
110ºC
38-8
370LF
60
2/0
110ºC
60-8
550LF,750LF
100
(#2)
110ºC
100-10
Chapter 2 Installation and Wiring