3-4
3.2 Test Run
This is the common connection example. Please refer to 4.1 Digital Operator, for the detailed use of the
digital operator (OPE-SR).
(1) To input the operation setting and the frequency setting from terminal control.
(Arrangements)
[1] Please make sure that the connections are correctly secure.
[2] Turn the ELB ON to supply power to the inverter.
(The red LED “POWER” on the digital operator should illuminate.)
[3] Set terminal with the frequency setting selection.
Set A001 as indication code, press the key once. (Two figures are shown.)
Set 01 with the key or the key, press the key once to set the frequency setting for
terminal. (Indication code turns back to A001.)
[4] Set terminal with the operation setting selection.
Set A002 as indication code, press the key once. (Two figures are shown.)
Set 01 with the key or the key; press the key once to set the operation setting for
terminal.
(Indication code turns back to A002.)
[5] Set monitor mode.
When monitoring the output frequency, set indication code to d001, and press the key once.
Or when monitoring the operating direction, set indication code to d003, press the key once.
[6] Input starting operation setting.
Turn ON between [FW] and [CM1] of terminal.
Impress voltage between [ O ] and [ L ] of terminal to start operation.
[7] Input ending operation setting.
Turn OFF between [FW] and [CM1] to stop slowly down.
1
2
1
2
Chapter 3 Operation
FUNC
STR
FUNC
FUNC
FUNC
Direct current reactor
Operating box
(OPE-4MJ2)
(OPE-8MJ2)
Alarm output contact
L
O
H
Motor
U
V
W
PD
P
RB
N
AL0
AL1
AL2
11A
11C
12C
12A
SP
SN
RP
SN
G
AMI
AM
L
O2
OI
O
H
P24
PLC
CM1
TH
FM
1
5
FW
R
S
T
Braking unit
R
S
T
Three Phase
Power supply
ELB
Digital operator
(RV)
Ground
STR