4-12
Frequency conversion monitor
This inverter displays the value changed by the Inverter output frequency
and the value set in b086 on the monitor part.
“Monitor part of display” = “ output frequency(d001)” x
“ output frequency
factor(b086)”
(Display) Display of d007
0.00 - 99.99: Display is in 0.01 unit.
100.0 - 999.9: Display is in 0.1 unit.
100. - 9999.: Display is in 1 unit.
1000 - 3996 :Display is in 10 unit.
(Range of setting) The setting range of b086
0.1 - 99.9 :Set it with the 0.1 unit.
(Example)Output frequency (d001):50.00Hz
When the frequency conversion factor (b086) is 1.1,
the frequency conversion monitor (d007) displays “55.00” as “50 x 1.1 = 55.00”.
(Note)Output frequency of FM terminal becomes same as d007 at the time of setting up
the digital output frequency to the FM terminal.
Output voltage monitor
This inverter displays the output voltage of the inverter converted into the
alternating Voltage.
The monitor lamp “V” should illuminate while the contents of d013 are displayed.
(Display)
0.0 – 600.0 :Display is in 0.1V unit.
Input electric power monitor
Display input electric power from inverter.
The monitor lamp “kW” (“V” and “A”) should illuminate while the contents of d014
is displayed.
(Display)
0.0 – 999.9 :Display is in 0.1kW unit.
Chapter 4 Explanation of function
d007: Frequency conversion
monitor
b086: Frequency conversion
factor
Relation code
d013: Output voltage
monitor
Relation code
d014: Input electric
power monitor
Relation code