4-48
Reset (RS)
This function resets the inverter when a protective trip has occurred.
The method of reset is to either push the STOP/RESET key on the
digital operator or to switch the RS terminal ON.
To reset the inverter with the control terminal, assign 18(RS) to an
intelligent input terminal.
Reset frequency matching selection C103 selects whether the inverter restarts
at 0Hz or the inverter matches the output frequency after the reset operation is complete.
Reset selection C102 selects when the alarm signal is cancelled and whether it is valid or invalid in normal
operation.
The RS terminal is valid only when the contact is set to NO.
Set item
Function
code
Data
Description
Retry waiting time
b003
0.3-100.
Units : seconds
(Reference to items of instantaneous power failure
or under-voltage)
After reset, time until restart is tried.
Frequency setting to match
b007
0.00-400.0
Units : Hz
(Reference to items of instantaneous stop/under-
voltage)
00
On ON signal, trip cancel (Example 1)
On normal, this is valid (output cuts off).
01
On OFF signal, trip cancel (Example 2)
On normal, valid (output cuts off)
Reset selection
C102
02
On ON signal, trip cancel (Example 1)
On normal, this is invalid. (only trip cancel)
00
0Hz start
Reset frequency matching
selection
C103
01
Frequency matching start. (Example 3)
Chapter 4 Explanation of function
b003 : Retry waiting time
b007 : Frequency setting to match
C102 : Reset selection
C103 : Reset frequency matching
selection
Relation code
RS
Alarm
(Example 1)
RS
Alarm
(Example 2)
(Example 3) When 01 (frequency matching) is selected with reset frequency matching selection C103,
it is also possible to operate frequency start on power ON again. And retry waiting time is
disregarded at the time of the setting C103:00 (0Hz start).
Number of motor
revolution time
Power supply
FW
Free-run
Frequency matching