4-44
Jogging operation(JG)
This function can be used to rotate the motor in small steps to
allow fine-tuning.
Set an intelligent input terminal to 06(JG).
(1) Jogging frequency
The jogging operation does not use acceleration, therefore it would be advisable to set the jogging frequency
to limit the starting current to a minimum or tripping may occur. Adjust A038 to the jogging frequency required.
Function
code
Data
Description
A038
0.0, start frequency-9.99
Units:Hz
(2) Jogging operation selection
Function
code
Data
Description
Jogging operation during run
Valid / Invalid
00
Free-run on jogging stop
01
Decelerating stop on jogging stop.
02
Direct braking on jogging stop.
Invalid (Example 1)
(Note 1)
03
Free-run on jogging stop.(example2)
04
Decelerating stop on jogging stop.
A039
(Note 2)
05
Direct braking on jogging stop.
Valid (Example 2)
(Note 1)
(Note 1) When using the jogging function, turn FW terminal or RV terminal ON after the JG terminal is turned
ON. (It is the same when the operation command point is from the operator.)
(Note 2) In the case that the setting of A039 is 02 or 05, data setting of DB is necessary.
When DB data is not setting,the inverter operates Free-run.
Chapter 4 Explanation of function
A038
: Jogging frequency
A039
: Jogging selection
C001-C005 : Intelligent input setting
Relation code
Free-run
JG
FW
JG
FW
(Example 1)
(Example 2)
Frequency command
Frequency command
When setting of A039 is 00,01 or 02 and FW
signal is turned ON beforehand, the inverter
doesn’t operate jogging.
When setting of A039 is 03,04 or 05 and FW
terminal is turned ON beforehand, the inverter
operates jogging. But jogging terminal is turned
ON beforehand, the inverter output is cut off.
JG
FW
RV
Output frequency
A038
0