3-6
[5] Set the output frequency
Set F001 as indication code, as press the key once.
(Indication code of four figures is shown.)
Set to the desired output frequency with the key or the key, press the key once to
store it.
(Indication code turns back to F001.)
[6]
Set the operation direction.
Set F004 as indication code, press the key once.
(00 or 01 is shown.)
Set operation direction to 00 in case of forward, or to 01 in case of reverse with the
key or the key. Press the key once to establish it.
(Indication code turns back to F004.)
[7] Set monitor mode.
When monitoring the output frequency, set indication code to d001, and press the key once.
Or when monitoring the operation direction, set indication code to d003, press the key once.
(Indication code are forward, reverse or stop.)
[8] Press the key to start operating.
(The green LED “RUN” turns on a light, and the indication changes in response to the monitor mode
set.)
[9] Press the key to decelerate to a stop.
(When the frequency turn back to 0, the green LED “RUN” light will switch off.)
Make sure that the direction of the motor is correct. It is in danger of injury or machine damage.
Make sure there is no abnormal noise and vibration. It is in danger of injury or machine damage.
Make sure that there is no tripping during the acceleration and deceleration and check that the revolution
per minute and the frequency meter are correct.
When overcurrent tripping or overvoltage tripping occurs during the test run, increase the acceleration time
or the deceleration time.
1
2
FUNC
1
2
RUN
Chapter 3 Operation
FUNC
FUNC
RESET
STOP/
FUNC
STR
STR
CAUTION