4-8
Function Mode
Code
Function name
Setting range
Initial data
-FE/-FU/-FR
Setting
on run
Change
mode on
run
Page
b021
Overload restriction
selection
00(invalid)/01(enabled on acceleration / constant speed)/02(enabled
on constant speed)
01
9
4-38
b022
Overload restriction level
0.50* rated current-1.50* rated current(A)
Rated
current of
inverter
x 1.20
9
4-38
b023
Overload restriction li mit
constant
0.10-30.00(s)
1.00
9
4-38
b024
Overload restriction 2
selection
00(invalid)/01(valid on acceleration / constant speed)/02(valid on
constant speed)
01
9
4-38
b025
Overload restriction level 2
0.50*rated current-1.50*rated current(A)
Rated
current of
inverter
x1.20
9
4-38
b026
Overload restriction
constant 2
0.10-30.00(s)
1.00
9
4-38
b031
Software lock mode
selection
00(i mpossible to change the data except this item when SFT terminal
is ON)/01(i mpossible to change the data except setting frequency
item when SFT terminal is ON)/02(i mpossible to change the data
except this item)/03(i mpossible to change the data except setting
frequency item)/10(possible to change data on operating)
01
9
4-45
b100
Free V/f frequency 1
0.- Free V/f frequency2(Hz)
0.
4-23
b101
Free V/f voltage 1
0.-800.0(V)
0.0
4-23
b102
Free V/f frequency 2
0.- Free V/f frequency3(Hz)
0.
4-23
b103
Free V/f voltage 2
0.-800.0(V)
0.0
4-23
b104
Free V/f frequency 3
0.- Free V/f frequency4(Hz)
0.
4-23
b105
Free V/f voltage 3
0.-800.0(V)
0.0
4-23
b106
Free V/f frequency 4
0.- Free V/f frequency5(Hz)
0.
4-23
b107
Free V/f voltage 4
0.-800.0(V)
0.0
4-23
b108
Free V/f frequency 5
0.- Free V/f frequency6(Hz)
0.
4-23
b109
Free V/f voltage 5
0.-800.0(V)
0.0
4-23
b110
Free V/f frequency 6
0.- Free V/f frequency7(Hz)
0.
4-23
b111
Free V/f voltage 6
0.-800.0(V)
0.0
4-23
b112
Free V/f frequency 7
0.-400.(Hz)
0.
4-23
b113
Free V/f voltage 7
0.-800.0(V)
0.0
4-23
C001
Intelligent input 1 setting
18
9
4-42
C002
Intelligent input 2 setting
16
9
4-42
C003
Intelligent input 3 setting
03/13/03
9
4-42
C004
Intelligent input 4 setting
02
9
4-42
C005
Intelligent input 5 setting
01/(RV:Reverse is valid)/02(CF1:Multi-speed1)/ 03(CF2:Multi-speed2)/
04(CF3:Multi-speed3)/ 05(CF4:Multi-speed4)/ 06(JG:Jogging)/
07(DB:External DC braking)/08(SET:2
n d
control)/
09(2CH:two-stage adjustable speed)/11(FRS:Free-run)/
12(EXT:External trip)/13(USP:Unattended start protection)/
14(CS:commercial change)/15(SFT:software lock)/
16(AT:Analog input voltage/current select)/18(RS:Reset inverter)/
20(STA:3wire run)/ 21(STP:3wire keep)/22(F/R:3wire forward/reverse)/
23(PID:PID selection valid/invalid)/24(PIDC:PID integrating reset)/
27(UP:Remote control UP function)/
28(DW N:Remote control DOW N function)/
29(UDC:Remote control data clear)/31(OPE:Force operate ope)/
32(SF1:Multi-speed bit1)/
33(SF2:Multi-speed bit2)/34(SF3:Multi-speed bit3)/
35(SF4:Multi-speed bit4)/36(SF5:Multi speed bit5)/
37(SF6:Multi-speed bit6)/38(SF7:Multi-speed bit7)/
39(OLR:Overload restriction change)/no(NO:No assign)
01
9
4-42
C011
Intelligent input1 a/b
(NO/NC) selection
00(NO)/01(NC)
00
9
4-42
C012
Intelligent input2 a/b
(NO/NC) selection
00(NO)/01(NC)
00
9
4-42
C013
Intelligent input3 a/b
(NO/NC) selection
00(NO)/01(NC)
00/01/00
9
4-42
C014
Intelligent input4 a/b
(NO/NC) selection
00(NO)/01(NC)
00
9
4-42
C015
Intelligent input5 a/b
(NO/NC) selection
00(NO)/01(NC)
00
9
4-42
C019
Input FW a/b (NO/NC)
Selection
00(NO)/01(NC)
00
9
4-42
C021
Intelligent output 11 setting
01
9
4-51
C022
Intelligent output 12 setting
00
9
4-51
C026
Alarm relay output
00(RUN:running)/01(FA1:Frequency arrivaltype1 signal)/
02(FA2:frequency arrival type2 signal)/03(OL:Overload advance
notice signal)/04(OD:Output deviation for PID control)/05(AL:Alarm
signal)/06(FA3:Only setting frequency)/08(IP:On instantaneous stop/
09(UV:Under voltage)/11(RNT:RUN time over)/12(ONT:ON time
over)/13(THM:thermal caution)
05
9
4-51
C027
FM selection
00(Output frequency)/01(Output current) /
03(Digital output frequency)/04(Output voltage)/
05(Input electric power)/06(thermal load rate)/07(LAD frequency)
00
9
4-56
C028
AM selection
00(Output frequency)/01(Output current)/04(Output voltage)/
05(Input electric power)/06(thermal load rate)/07(LAD frequency)
00
9
4-57
C029
AMI selection
00(Output frequency)/01(Output current)/04(Output voltage)/
05(Input electric power)/06(Thermal load rate)/07(LAD frequency)
00
9
4-57
C031
Intelligent output 11 a/b
00(NO)/01(NC)
00
9
4-52
C032
Intelligent output 12 a/b
00(NO)/01(NC)
00
9
4-52
C036
Alarm relay output a/b
00(NO)/01(NC)
01
9
4-52
C040
Overload advance notice
signal output mode
00(On accel. And decel, constant speed)/01(Only constant speed)
01
9
4-39
C041
Overload advance notice
level
0.0-2.0*rated current(A)
Inverter
rated current
9
4-38
C042
Frequency arrival setting
for acceleration.
0.00-99.99/100.0-400.0(Hz)
0.00
9
4-53
C043
Arrival frequency setting for
deceleration.
0.00-99.99/100.0-400.0(Hz)
0.00
9
4-53
C044
PID deviation setting level
0.0-100.0(%)
3.0
9
4-31
Chapter 4 Explanation of function
O
v
erl
o
ad
l
im
it
Lo
c
k
F
ree
V
/f sett
ing
In
te
lli
gen
t i
npu
t
te
rm
in
a
l sett
in
g
In
put t
e
rm
ina
l set
ti
ng
in
te
ll
ig
e
n
t
Ou
tput
term
in
a
l st
ate se
tt
in
g
Ou
tput l
e
ve
l
set
ti
ng
In
te
lli
gen
t out
put t
e
rm
ina
l
s
e
tti
n
g