4-15
Operation command selection
Select the control of RUN/STOP commands.
Operation command from the control terminals (Terminal)
tart/Stop by ON/OFF of control terminals.
Forward : FW-CM1 terminal
Reverse : RV-CM1 terminal
Put 01(RV) to an intelligent Input terminal.
When using the FW terminal, it is possible to change the contact from NO to NCby settin a or b (respectively)
in C019.When operating from the digital operator, set operation direction in F004.Or operate Start/Stop with
RUN key/STOP key on the digital operator.It becomes stop command when proper forword command and
reverse command are inputted at the same time.
Set item
Function code
Data
Contents
01
Start/Stop with control terminals(Terminal).(FW, RV)
02
Start/Stop with digital operator, remote operator.
03
Start/Stop with RS485 terminals for communications.
04
Start/Stop with option board 1.
Operation
command
selection
A002
05
Start/Stop with option board 2.
00
a contact (NO)
Input FW a/b
(NO/NC)
selection
C019
C011-C015
01
b contact (NC)
Selection on stop
When stop is commanded from the digital operator or the control
terminals (Terminal), select the stop after slowing-down according to
slowing-down time or the free run stop.
When the second cycle is started while in free run stop, the inverter
follows the free-run stop selection b088 and restarts.
(Refer to the item of free-run stop.)
Set item
Function
code
Data
Contents
00
Normal stop (Decelerated stop)
Selection on Stop
b091
01
Free-run stop
00
0Hz start
Selection of free-run stop
b088
01
Start frequency matching
Frequency setting to match
b007
0.00-400.0
Unit : Hz
Waiting time for retrying
b003
0.3-100.
Unit : second
Selection of Stop key
Even though the control terminals are selected for the operation command,
you can still set whether the stop key of operator (digital operator etc) is
effective or not. Trip reset functions by the stop key follows this establishment,
too.
Function code
Data
Contents
00
The stop key is effective.
b087
01
The stop key is ineffective.
b087: Selection of stop key
Relation code
b091 :Selection on stop
F003/F203: 1
st
/2
nd
deceleration time
b003 :Waiting time for retrying
b007 :Frequency setting to match
b088 :Select for free-run stop
Relation code
A002 :Operation command selection
C001-C005: Input intelligent terminal
C019 :Inputting FW a/b (NO/NC) selection
F004 :Operation direction select
Relation code
Chapter4 Explanation of function