4-55
RUN time / power ON time over (RNT/ONT)
When the accumulated operation time reaches or is over the
Setting time in b034, RUN time/power ON time over (RNT/ONT)
output is switched.
Function
code
Data
Description
b034
0.
1. -9999.
1000-6553
Don’t operate.
Set by 10-hour unit.
Set by 100 hours unit. (10000-65530 hours)
(1) Run time over (RNT)
Assign 11(RNT) to an intelligent output terminal 11, 12 (C021, C022) or the alarm relay output terminal
(C026).
Set ON time level with b034.
(2) Power ON time over (ONT)
Assign 12(ONT) to an intelligent output terminal 11, 12 (C021, C022) or the alarm output terminal, (C026).
Set ON time level with b034.
Force operation ope function
This function is used to operate from the operator forcibly by on/off
of an intelligent terminal when frequency and operation command
is selected other than the operator.
Becoming the operation from the frequency and operation command that was selected by A001 and A002 if
the signal is off, and becoming the frequency and operation command from an operator forcibly if the signal is
on when the compulsion operation function is selected by an intelligent input selection.
When changed the operation command while driving, operation command is canceled and become stoppage
at first.
Operation command from each command input the operation command once again as the stoppage at first for
driving once again.
Setting item
Function cord
Setting value
Contents
Frequency command selection
A001
00
01
02
03
04
05
Potentiometer the digital operator has
Terminal
Operator
RS485
Option 1
Option 2
Operation command selection
A002
01
02
03
04
05
Terminal
Operator
RS485
Option 1
Option 2
Intelligent input selection
C001-C005
31
OPE : Compulsion operation
Relation code
Chapter 4 Explanation of function
b034 : Warning time level
C021,C022: Intelligent output terminal
C026 : Alarm relay output terminal
d016 :Accumulation time monitor during RUN
d017 :Power ON time monitor
Relation code
A001: Frequency setting selection
A002: Operation command selection
C001-C005: Intelligent input terminal