4-54
(1) Output on constant speed arrival (01:FA1)
When the inverter arrives at the set frequency with frequency setting (F001, A020,A220) or multi-speed
(A021-A035),
the output relay is switched.
(2) Output over setting frequency (02:FA2)
When the output is over the arrival frequency set in C042, C043 on adjustable speed time, the output
relay is switched.
(3) Output setting frequency (06:FA3)
The signal is switched only when the output frequency matches the arrival frequency set in C042, C043
on adjustable speed time.
Chapter 4 Explanation of function
Setting frequency
(Example) max. frequency f max=120(Hz)
setting frequency f set=60(Hz)
f
on
=120
x
0.01=1.2(Hz)
f
off
=120
x
0.02=2.4(Hz)
On acceleration: ON with 60 - 1.2=58.8(Hz)
On deceleration: OFF with 60 - 2.4=57.6(Hz)
FA1
Output
frequency
f
Off
f
On
F
on
: 1% of maximum frequency
F
off
: 2% of maximum frequency
f
On
: 1% of max. frequency
f
Off
: 2% of max. frequency
FA2
Output
frequency
f
Off
f
On
C042
C043
FA3
Output
frequency
f
Off
f
On
C042
C043
f
On
f
Off
f
On
: 1% of max. frequency
f
Off
: 2% of max. frequency