4-68
(vi) 05 command: This reads trip history data.
• Transmission frame
Frame format
Explanation
Data size
Value
STX
Control code(Start of TeXt)
1 byte
STX (0x02)
Cord
Station number of inverter
2 byte
01-32
Command
Transmission command
2 byte
05
BCC
Block check code
2 byte
Exclusive OR of Code, Command and
Data (5) Reference
CR
Control code(Carriage Return)
1 byte
CR (0x0D)
Replay frame
Frame format:
Explanation
Data size
Value
STX
Control code(Start of TeXt)
1 byte
STX (0x02)
Code
Station number of inverter
2 byte
01-32
Data
Each monitor data on trip
440 byte
(Note 8) reference
BCC
Block check code
2 byte
Exclusive OR of Code, Command and Data
(5) Reference
CR
Control code(Carriage Return)
1 byte
CR (0x0D)
Note 8) The monitor data (trip history) on trip memorizes the last six errors with an accumulated count
number (8byte).
_ _ _
STX
Code
Command
BCC
CR
STX
Code
Data
BCC
CR
Accumulated
count number
Trip history 1
Trip history 6
Monitor item
Units
Magnifi
cation
Data
size
Notes
Trip factor
-
-
8byte
Cord display
Inverter status A)
-
-
8byte
Inverter status B)
-
-
8byte
Inverter status C)
-
-
8byte
04 command
Note 7 reference
Output frequency
Hz
x10
8byte
Tenth ASCII code
Output current
A
x10
8byte
Tenth ASCII code
Current voltage
V
x10
8byte
Tenth ASCII code
Accumulated RUN time
hour
x 1
8byte
Tenth ASCII code
Power source ON time
hour
x1
8byte
Tenth ASCII code
U
p
per
Low
er
Chapter 4 Explanation of function