4-45
Second control function(SET)
This control function is used when the Inverter is connected to two different types of motors. By assigning
08(SET) to an intelligent input terminal and turning SET terminal ON/OFF you can switch between two different
Inverter set-ups.
Select 2
nd
control function while the Inverter is in the STOP condition.
The functions which can change with SET terminal
F002/F202 : 1
st
/ 2
nd
acceleration time
F003/F203:1
st
/ 2
nd
deceleration time
A003/A203:1
st
/ 2
nd
base frequency
A004/A204:1
st
/ 2
nd
max. frequency
A20/A220:1
st
/ 2
nd
multi-speed 0 setting
A041/A241:1
st
/ 2
nd
torque boost selection
A042/A242:1
st
/ 2
nd
manual torque boost
A043/A243:1
st
/ 2
nd
manual torque boost point
A044/A244:1
st
/ 2
nd
control system
A061/A261:1
st
/ 2
nd
frequency maxmum limiter
A062/A262:1
st
/ 2
nd
frequency minimum limiter
A092/A292:1
st
/ 2
nd
acceleration time 2
A093/A293:1
st
/ 2
nd
deceleration time 2
A094/A294:1
st
/ 2
nd
two-stage adjustable speed selection
A095/A295:1
st
/ 2
nd
two-stage acceleration frequency
A096/A296:1
st
/ 2
nd
two-stage deceleration frequency
b012/b212:1
st
/ 2
nd
electronic thermal level
b013/b213:1
st
/ 2
nd
electronic thermal characteristic selection
H003/H203:1
st
/ 2
nd
allowable motor selection
H004/H204:1
st
/ 2
nd
allowable motor pole selection
H006/H206:1
st
/ 2
nd
stabilized constant
Display during setting isn’t differentiated between the 1
st
control function or the 2
nd
control function. So confirm
it in the state of ON/OFF of termnal.
Even if 1
st
/ 2
nd
control is changed during run, it will not be active until the inverter is stopped.
Software lock mode selection(SFT)
This function is used to prevent changing data by mistake.
When you want to use an intellignent input terminal, assign 15(SFT).
Below is the software lock code selection.
Function code
Data
SFT
terminal
Description
00
ON/OFF
Write disable except for b031/write enable
01
ON/OFF
Write disable except for b031,F001,A020,A220,
A021~A035,A038 / write enable
02
-
Write disable except for b031
03
-
Write disable except for b031,F001,A020,A220,
A021~A035,A038
b031
10
-
Write disable except for change mode during running (code
list reference)
Chapter 4 Explanation of function
Motor1
Motor2
Inverter
U
V
W
SET
CM1
b031 :Software lock mode selection
C001-C005: Intelligent input setting
Relation code