4-5
4.2 Code list
Monitor code
Dis-
play
code
Function name
L300P monitor or data range
(digital operator)
Initial
data
Setting
on
running
Change
mode
during
running
Page
d001
Output frequency
monitor
0.00-99.99/100.0-400.0(Hz)
-
-
-
4-10
d002
Output current
monitor
0.0-999.9(A)
-
-
-
4-10
d003
Operation direction
monitor
F(forward)/o(stop)/r(reverse)
-
-
-
4-10
d004
PID feedback
monitor
0.00-99.99/100.0-999.9/1000. -9999. /
1000-9999/ 100- 999 (10000-99900)
-
-
-
4-10
d005
Intelligent input
terminal monitor
-
-
-
4-11
d006
Intelligent output
terminal monitor
-
-
-
4-11
d007
Frequency
conversion monitor
0.00-99.99/100.0-999.9/1000. –9999. /
1000-3996
-
-
-
4-12
d013
Output voltage
monitor
0.0-600.0 V
-
-
-
4-12
d014
Electric power
monitor
0.0-999.9 kW
-
-
-
4-12
d016
Accumulated time
monitor during RUN
0.-9999./1000-9999/ 100- 999 h
-
-
-
4-13
d017
Power ON time
monitor
0.-9999./1000-9999/ 100- 999 h
-
-
-
4-13
d080
Number of trip time
monitor
0.-9999./1000-6553(10000-65530) (time)
-
-
-
4-13
d081
Trip monitor 1
Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)
-
-
-
4-13
d082
Trip monitor 2
Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)
-
-
-
4-13
d083
Trip monitor 3
Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)
-
-
-
4-13
d084
Trip monitor 4
Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)
-
-
-
4-13
d085
Trip monitor 5
Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)
-
-
-
4-13
d086
Trip monitor 6
Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)
-
-
-
4-13
d090
Warning monitor
Warning code
-
-
-
4-78
F001
Output frequency
setting
0.0, starting frequency-Max. frequency
(2
nd
max. frequency)(Hz)
0.00
9
9
4-14
F002
1
st
acceleration time
0.01-99.99/100.0-999.9/1000.-3600.(s)
30.00
9
9
4-16
F202
2
nd
acceleration time
0.01-99.99/100.0-999.9/1000. -3600. (s)
30.00
9
9
4-16
F003
1
st
deceleration time
0.01-99.99/100.0-999.9/1000. -3600. (s)
30.00
9
9
4-16
F203
2
nd
deceleration time
0.01-99.99/100.0-999.9/1000. -3600. (s)
30.00
9
9
4-16
F004
Operation direction
selection
00(forward)/01(reverse)
00
4-15
(Note 1) Change mode during run by selection of b031 (software lock selection).
(Note) Do not forget to press “STR” key when you change the display.
Chapter 4 Explanation of function
(Note 1)
(Example) FW, terminal2, and 1: ON
Terminal 5, 4, 3 :OFF
ON
OFF
5 4
3 2
1
FW
(Example) Terminal2, 1:ON
AL :OFF
ON
OFF
12
11
AL