iv
UL Warnings and Cautions Manual for L300P series
This auxiliary instruction manual should be delivered to the end user.
1.Wiring Warnings for Electrical Practices and Wire Specifications
(1)
! WARNING
:
"Use 60/75 ºC CU wire only" or equivalent.
(2)
! WARNING
:
"Open Type Equipment."
For models with L300P 900-1320H.
(3)
! WARNING
:
"Suitable for use on a circuit capable or delivering not more than 10,000 rms
symmetrical amperes, 240 V maximum." For models with suffix L.
(4)
! WARNING
:
"Suitable for use on a circuit capable or delivering not more than 10,000 rms
symmetrical amperes, 480 V maximum." For models with suffix H.
2.Tightening Torque and Wire Range
(1)
! WARNING
:
Tightening torque and wire range for field wiring terminals are marked
adjacent to the terminal or on the wiring diagram.
Model Name Tightening Torque [N•m] Wire Range (AWG)
L300P-110L
4.9
4
L300P-150L
4.9
2
L300P-185L
4.9
1
L300P-220L
8.8
1/0
L300P-300L
8.8
2/0
L300P-370L
8.8
3/0 or 2 parallel of 1 AWG
L300P-450L
13.7
250kcmil or 2 parallel of 1 AWG (75ºC)
L300P-550L
13.7
350kcmil or 2 parallel of 1/0 AWG
L300P-750L
13.7
350kcmil or 2 parallel of 1/0 AWG
L300P-110H
4.9
8
L300P-150H
4.9
6
L300P-185H
4.9
6
L300P-220H
4.9
4
L300P-300H
4.9
3
L300P-370H
4.9
1