4-79
4.4.3 Warning Monitor display
Warning messages will appear when the data set is contradicting to others.
Program lamp (PRG) turns ON during the warning (until the data is changed).
Below is the description of the warnings.
Warning
Codes
<, >
Basic code
001/ 201
frequency upper limiter A061/A261
>
002/ 202
frequency lower limiter A062/A262
>
004/ 204
Base frequency A003/A203 (Note 1)
>
005/ 205
Output frequency F001, Multi stage speed 0 A020/A220
>
006/ 206
Multi stage speed 1~15 A021~A035
>
Maximum frequency
A004/A204
012/ 212
frequency upper limiter A062/A262
>
015/ 215
Output frequency F001, Multi stage speed 0 A020/A220
>
016/ 216
Multi stage speed 1~15 A021~A035
>
frequency upper limiter
A061/A261
021/ 221
frequency upper limiter A061/A261
<
025/ 225
Output frequency F001, Multi stage speed 0 A020/A220
<
frequency lower limiter
A062/A262
031/ 231
frequency upper limiter A061/A261
<
032/ 232
frequency lower limiter A062/A262
<
035/ 235
Output frequency F001, Multi stage speed 0 A020/A220
<
036
Multi stage speed 1~15 A021~A035
<
037
Jogging frequency A038
<
Starting frequency b082
085/ 285
Output frequency F001, Multi stage speed 0 A020/A220
<>
086
Multi stage speed 1~15 A021~A035
<>
Jump frequency 1/2/3
+- Jump width
A063+-A064
A065+-A066
A067+-A068 (Note 2)
091/ 291
frequency upper limiter A061/A261
>
092/ 292
frequency lower limiter A062/A262
>
095/ 295
Output frequency F001, Multi stage speed 0 A020/A220
>
096
Multi stage speed 1~15 A021~A035
>
Free v/f frequency 1~6 b100, b102, b104, b106, b108, b110
>
Free v/f frequency 7 b112
Free v/f frequency 2~6 b102, b104, b106, b108, b110
<
Free v/f frequency 1 b100
Free v/f frequency 1 b100
>
Free v/f frequency 3~6 b104, b106, b108, b110
<
Free v/f frequency 2 b102
Free v/f frequency 1, 2 b100, b102
>
Free v/f frequency 4~6 b106, b108, b110
<
Free v/f frequency 3 b104
Free v/f frequency 1~3 b100, b102, b104
>
Free v/f frequency 5, 6 b108~b110
<
Free v/f frequency 4 b106
Free v/f frequency 1~4 b100, b102, b104, b106
>
Free v/f frequency 6 b110
<
Free v/f frequency 5 b108
110
Free v/f frequency 1~5 b100, b102, b104, b106, b108
>
Free v/f frequency 6 b110
Free electronic thermal frequency 2, 3 b017, b019
<
Free electronic thermal
frequency 1 b015
Free electronic thermal frequency 1 b015
>
Free electronic thermal frequency 3 b019
<
Free electronic thermal
frequency 2 b017
120
Free electronic thermal frequency 1, 2 b015, b017
>
Free electronic thermal
frequency 3 b019
Warning is cleared when the setting fulfils the above condition.
Data will be changed automatically to the basic code.
(Note 1) In case of this, the Base frequency will be changed to Maximum frequency. Because it has the
possibility that the motor is damaged according to the value, please set the correct data when the
004/ 204 will appear.
(Note 2)
The jump frequency will be automatically re-written to the lowest jump frequency (= Jump frequency
– jump width)
Chapter 4 Explanation of function
d090 : Warning Monitor
Relation code