(2) Overload advance notice
When the load is high, it is possible to adjust the load again by outputting an overload advance notice.
It is used to prevent damage to the machine from too much load, i.e. baggage on a conveyor, the Inverter
overload protection will operate.
Assign 03(OL) to an intelligent output terminal 11, 12 or the alarm relay output terminal.
Set item
Function
code
Data
Description
00
On acceleration, constant speed, this is valid.
Overload
advance notice
signal output
mode selection
C040
01
On constant speed only, this is valid.
0.0
Overload advance notice is non-effective.
Overload
advance notice
level
C041
0.1 to
Rated current x
2.0
Units: A
As load reaches overload advance notice level,
OL signal is output.
Overload advance notice level
C040
Output current
OL
Inverter output frequency
Overload restriction level
b022/b025
Output frequency
Goal frequency
F001
Deceleration set with
overload restriction constant
b023/b026
Maximum frequency
A004/A204
Overload restriction level
b022/b025
Chapter 4 Explanation of function