4-52
Intelligent output terminal a/b (NO/NC)selection
This sets the intelligent output terminal 11,12 and alarm
relay output terminal contact condition to either NO or NC,
(a or b).
Each output is changeable individually.
Both intelligent output terminals 11 and 12 and the alarm relay are all relay outputs.
Set item
Function code
Data
Description
00
A contact(NO)
Intelligent output 11,12
A/b(NO/NC) selection
C031-C032
01
B contact(NC)
Contact specification
AC 250V 5Amax
00
A contact(NO)
Alarm relay output
A/b(NO/NC)selection
C036
01
B contact(NC)
Contact specification
AL1-AL0:AC 250V 5Amax
AL2-AL0:AC 250V 2Amax
a contact: Close with {ON}, open with {OFF}.
b contact: Open with {ON}, close with {OFF}.
(1) Specification of the intelligent output terminals 11 and 12
Specification of the intelligent output terminals 11 and 12 is as follows;
C031,
C032
Set value
Power supply Output description
State of output
terminal 11
or 12 terminal
ON
Close
On
OFF
Open
00
(a contact)
Off
-
Open
ON
Open
On
OFF
Close
01
(b contact)
Off
-
Open
(2) Specification of the alarm relay output terminal
The specifications of the alarm relay output terminal is a changeover contact. Action is as follows.
Example on using as alarm
State of output
terminal
C036
Set value
Power
source
State of
inverter
AL1-AL0 AL2-AL0
On abnormal
Close
Open
On
On normal
Open
Close
00
(a contact)
Off
-
Open
Close
On abnormal
Open
Close
On
On normal
Close
Open
01
(b contact)
Off
-
Open
Close
C031-C032: Intelligent output 11,12a/b (NO/NC)
selection
C036 : Alarm relay output a/b (NO/NC) selection
Relation code
Chapter 4 Explanation of function
Inverter inside
11C 11A
12C 12A
- - -
ALO AL1 AL2
Inverter inside
Resistor
load
Inductor
load
Maximum
AC250V, 5A
DC30V, 5A
AC250V, 1A
DC30V, 1A
Minimum
DC1V 1mA
Contact Specification
Resistor load
Inductor load
Maximum
AC250V, 2A
DC30V, 8A
AC250V, 0.2A
DC30V, 0.6A
AL1-AL0
Minimum
AC100V, 10mA
DC5V, 100mA
Maximum
AC250V, 1A
DC30V, 1A
AC250V, 0.2A
DC30V, 0.2A
AL2-AL0
Minimum
AC100V, 10mA
DC5V, 100mA
Contact Specification