6-2
400V class
Inverter Model
L300P
110HF
L300P
150HF
L300P
185HF
L300P
220HF
L300P
300HF
L300P
370HF
L300P
450HF
L300P
550HF
L300P
750HF
L300P
900HF
L300P
1100HF
L300P
1320HF
Enclosure
(Note 1)
IP20(NEMA1)
IP00
Max. Applicadie Motor 4P
(kW) (Note 2)
11
15
18.5
22
30
37
45
55
75
90
110
132
400V
15.2
20.0
25.6
29.7
39.4
48.4
58.8
72.7
93.5
110.8
135.0
159.3
Rated input
Alternating
voltage(kVA)
480V
18.2
24.1
30.7
35.7
47.3
58.1
70.1
87.2
112.2
133.0
162.1
191.2
Rated input alternating
Voltage
Three-phase 380-480V (±10%) 50Hz/60Hz
Rated output voltage
(Note 3)
Three-phase 380-480V (This corresponds to receiving voltage.)
Rated output current (A)
22
29
37
43
57
70
85
105
135
160
195
230
Control system
Sine-wave modulation PWM system.
Output frequency range
(Note 4)
0.1-400Hz
Frequency accuracy
Digital command ±0.01% for Max. frequency, analog frequency ±0.2%(25±10ºC)
Frequency resolving
Power
Digital setting: 0.01Hz, analog setting: Max. frequency /4000
Voltage/frequency
characteristic
V/f option variable, V/f control, (constant torque, reduced torque)
Overload current rate
120% for 60 seconds, 150% for 0.5second
Acceleration/
Deceleration time
0.01-3,600seconds (straight or S-Curve on acceleration, deceleration is optional setting individually), 2
nd
adjustable setting is possible.
Regenerative
Control
(short duration)
(Note 5)
BRD circuit built-in
(Discharge resis-tance is
required.)
Regenerative unit is required.
C
ontrol
DC Braking
On starting and decelerating by stop command, inverter operates under operation setting frequency. Or inverter operates with external input
(Breaking power, time, frequency can be set.)
Operator
Setting by keys
Volume
Setting with potentiometer on the digital operator (Built-in as standard) (Analog setting)
External
Signal
DC 0 to 10V, -10 to +10V (input impedance 10k ohm), 4 to 20mA (input impedance 100 ohm)
Freq-
uency
External
port
Setting with RS485 communication
Operator
Run/Stop (forward changes with code)
External
signal
Forward Run/Stop (1a connect), reverse command is impossible on assigning of terminal (selection of 1a, 1b is possible), input of 3 wires is possible.
Run/
Stop
External
port
Setting with RS485.
Intelligent input
Terminal
Use by selecting terminals from;
Reverse command (RV), multi-speed1-4 (CF1-CF4), jogging (JG), external dc braking (DB), 2
nd
control (SET),2
nd
acceleration (2CH), free-run stop (FRS), external trip (EXT),
USP function (USP), commercial change (CS),software lock (SFT), analog input voltage / current / select (AT), reset inverter (RS), 3 wire run (STA),3 wire keep (STP),
3 wire direction selection (F/R), PID selection valid/invalid (PID), PID integrating reset (PIDC), remote control,up function (UP), remote control down function (DWN),
remote control data clear (UDC), multi-speed bit 1-7(SF1-SF7),overload ristriction change (OLR), no assign (NO)
Input si
gnal
Thermistor input
Terminal
1 terminal
Intelligent output
Terminal
2 relay outputs (1a contact), relay(1c contact), output relay selection as follows;
(selection from during running, on arrival with constant speed, over setting frequency, PID over-deviation)
Output
il Intelligent monitor
Output terminal
Analog voltage output, analog current output, pulse line output
Display monitor
Output frequency, output current, frequency conversion value, trip history, input output terminal state, input electric power, output voltage.
Other function
V/f free setting (5 points), Upper / lower frequency limitter, Frequency jump, Curve adjustable speed, Manual torque boost level / Braking point,Analog meter adjustment,
Starting frequency, Carrier frequency adjustment, Electronic thermal free setting, External start/end (frequency/rate),Analog input selection, Trip retry, Reduced voltage start,
Overload restriction
Carrier frequency
Range
0.5-12 kHz
0.5-8 kHz
Protection function
Over-current, over-voltage, under-voltage, electronic thermal level, abnormal trouble, ground fault current on starting, instantaneous stop, USP error, open-phase error, control resistor
overload, CT error, external trip, communication error
Frequency
temperature
/Preservation
temperature
(Note 6) /humidty
-10 to 40ºC (Note 10) / -20 to 65ºC / 20 to 90% RH (installed with no dew condensation)
Vibration (Note 7)
5.9m
2
/ S (0.6G), 10-55Hz
2.94m
2
/ S (0.3G), 10-55Hz
U
sage
surroundi
ngs
Using place
Under 1,000m above sea level, indoors (installed away from corrosive gasses, dust)(Note 8)
Paint color
Blue (D.I.C14 version No.436)
Gray (MUNSELL 8.5YR6.2/0.2)
Options
Operator with copy function, cable for operator, braking resistor, regenerative control unit, alternating reactor, D.C. reactor, EMC Mains filter, higher harmonic
control unit, LCR filter, applied control installation
Remote operator
OPE-SR, cable for remote operation ICS-1(1m), ICS-3(3m) (Note 9)
Schematic mass (kg)
5
5
12
12
12
20
30
30
30
60
60
80
(Note 1) Protective system bases on JME1030.
(Note 2) Applicable motor indicates HITACHI three-phase motor. When you use other motor, set so that the motor current doesn’t exceed the rated current of the inverter.
(Note 3) Output voltage will reduce when the power voltage is reduced. (Except when AVR function is selected.)
(Note 4) When you operate motor over 50/60Hz, inquire about the allowable max.revolution time of motor etc. from motor manufacturer.
(Note 5) Braking resistance isn’t installed in the inverter. When the inverter requires a high regenerative torque, use optional braking resistance and regenerative braking unit.
(Note 6) Protective temperature is temperature during transportation.
(Note 7) This bases on the test methods of JIS C0911(1984).
(Note 8) When the inverter is used in a place with dust, we recommend the optional varnish coating specification. Before it is required.
(Note 9) When you use cable for remote operation, please remove connector. Please refer to 1.3 Appearance.
(Note 10) When using at 50ºC of ambient air temperature, the rated output current will be reduced. (P.4-18)
(Note ) Insulation distance is based on UL, CE standard.
Chapter 6 Specification